Reading the Status Indicators

The six lights on the left side of the monitor panel are status indicators. They are backlit by colored light emitting diode (LED) lamps, and work in conjunction with the alarm horn to let you know the operating status of the UPS.

Normal This green indicator is lit when the UPS is operating in Normal mode. The power processing unit (PPU) is supplying power to the critical load.

Battery This yellow indicator is lit when the UPS is operating in Battery mode. Because Battery mode is a normal condition of the UPS, the Normal indicator also remains lit.

Bypass This yellow indicator is lit when the UPS is operating in Bypass mode. The critical load is supported by the bypass source. The Normal indicator is not lit when the system is in Bypass mode.

Notice This yellow indicator is lit when the system needs attention. The LCD screen shows all active notices. Some notices may be accompanied by

an audible horn. To silence the horn, press the and pushbuttons simultaneously. The Notice indicator may be lit along with other indicators.

Alarm This red indicator is lit when a situation requires immediate attention. The LCD screen shows the highest priority active alarms. All alarms are accompanied by an audible horn. To silence the horn, press the

and pushbuttons simultaneously. The Alarm indicator may be lit along with other indicators.

Standby This yellow indicator is lit when electricity is present in the PPU of the UPS and the Normal indicator is not lit. During normal startup, this indicator illuminates until the UPS transfers to Normal mode, at which point the Normal indicator is lit. During normal shutdown, the Standby indicator is lit until all energy in the UPS is dissipated and shutdown is complete.

For more information about audible horns, refer to the System Event Horns section of Chapter 12.

To test the LED lamp status indicators, press the and pushbuttons simultaneously for 3 seconds. All the indicators should light while you hold down these pushbuttons. If any indicator does not light, its LED may need to be replaced. Contact Customer Service if you have a problem with the indicator lamps.

 

 

 

54

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Page 62
Image 62
Powerware 5075 kVA operation manual Reading the Status Indicators