System Output
Rectifier/Charger Capacity | 135% + 6 Kw |
|
|
DC Filtering | Ripple voltage less than 0.5% peak to peak |
|
|
UPS Output Capacity | 100% current at 0.8 power factor |
|
|
Output Voltage Regulation | 1% (10% to 100% load) |
|
|
Output Voltage Adjustment | 480 VAC nominal, adjustable from 452 VAC |
| to 508 VAC (60 Hz only) |
|
|
Output Voltage Harmonic Content | 2% max THD, 2% max single (for linear load) |
|
|
Output Voltage Balance | 2% for 100% maximum load imbalance |
|
|
Output Voltage Phase | 2˚ for 100% maximum load imbalance |
Displacement |
|
|
|
Output Transients | 5% for 100% load step or removal |
|
|
Frequency Regulation | 0.005 Hz free running |
|
|
Synchronous to Bypass | Bypass within voltage limits of +5%, |
| output setting; bypass within 0.5 Hz |
|
|
Frequency Slew Rate | 1 Hz per second maximum |
|
|
Overload Capability | Up to 125% for 15 minutes |
| Above125% for 30 seconds |
| 1000% for 10 cycles with bypass |
|
|
Maximum Output Capability | 300% peak for 10 cycles without bypass |
|
|
122 | Powerware BPIII Harsh Environment UPS |