System Output

Rectifier/Charger Capacity

135% + 6 Kw

 

 

DC Filtering

Ripple voltage less than 0.5% peak to peak

 

 

UPS Output Capacity

100% current at 0.8 power factor

 

 

Output Voltage Regulation

1% (10% to 100% load)

 

 

Output Voltage Adjustment

480 VAC nominal, adjustable from 452 VAC

 

to 508 VAC (60 Hz only)

 

 

Output Voltage Harmonic Content

2% max THD, 2% max single (for linear load)

 

 

Output Voltage Balance

2% for 100% maximum load imbalance

 

 

Output Voltage Phase

2˚ for 100% maximum load imbalance

Displacement

 

 

 

Output Transients

5% for 100% load step or removal

 

 

Frequency Regulation

0.005 Hz free running

 

 

Synchronous to Bypass

Bypass within voltage limits of +5%, ---8% of

 

output setting; bypass within 0.5 Hz

 

 

Frequency Slew Rate

1 Hz per second maximum

 

 

Overload Capability

Up to 125% for 15 minutes

 

Above125% for 30 seconds

 

1000% for 10 cycles with bypass

 

 

Maximum Output Capability

300% peak for 10 cycles without bypass

 

 