25.Table I lists the maximum rating for DC input circuit protection devices (circuit breakers).
Table I. Maximum DC Input Circuit Breaker Ratings
Balanced Power System | All Voltage Ratings |
|
|
Balanced Power 75 | 700 |
|
|
Balanced Power 62.5 | 600 |
Balanced Power 50 | 450 |
26.Your UPS equipment’s operating environment must meet the size and weight requirements shown in Table J, according to your UPS system configuration:
Table J. Equipment Weight and Point Loading |
| |
| Weight | Point Loading |
Component | Kg (lb) | Kg (lb) |
UPS and Environmental Cabinets
1878 (4140)
8 at 235 (518)
27.The basic environmental requirements for operation of the UPS system are: Ambient Temperature Range:
DESCRIPTION: INSTALLATION NOTES
DRAWING NO: |
SHEET: 7 of 11
|
|
|
| REVISION: B | DATE: 011500 |
| |
|
|
|
|
| |||
|
| ||||||
Powerware BPIII Harsh Environment UPS |