Powerware 5075 kVA operation manual 100.1 74.7 171.5

Models: 5075 kVA

1 162
Download 162 pages 48.55 Kb
Page 154
Image 154

100.1

(3.94)

74.7

(2.94)

171.5

(6.75)

KNOCKOUTS PROVIDED

ON FIVE SURFACES

25.4

(1.00)

FLUSH MOUNT

.75

41.1

(1.62)

88.9

(3.50)

190.5

(7.50)

CONDUIT AND WIRING SUPPLIED BY CUSTOMER. MAX. DISTANCE BETWEEN REMOTE MONITOR AND UPS NOT TO EXCEED 500 FEET.

285.7

(11.25)

215.9

(8.50)

MAX. WIRE SIZE: NO. 14 AWG

MIN. WIRE SIZE: NO. 18 AWG

216.58

(8.50)

197.47

(7.75)

SURFACE

MOUNT (FOR HANGING)

WIRES MUST BE TWISTED (14---18 gauge)

Dimensions are in millimeters (inches)

DESCRIPTION:

REMOTE MONITOR PANEL

DRAWING NO:

164201261---7

 

SHEET: 1 of 1

REVISION: A

 

DATE:

053099

A---22

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503