16.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 1.8 volts per cell.

17.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.

18.A battery disconnect switch is recommended, and may be required by NEC or local codes when batteries are remotely located. The battery disconnect switch may be supplied as an accessory, and should be installed between the battery and the UPS.

19.Table G lists the maximum rating for input circuit protective devices (circuit breakers).

Table G. Maximum Input Circuit Breaker Ratings

Balanced Power System

 

Input Voltage Rating

 

 

 

 

 

208V

400V

480V

600V

 

 

 

 

 

 

Balanced Power 75

400

N/A

175

150

 

 

 

 

 

Balanced Power 62.5

350

175

150

125

 

 

 

 

 

Balanced Power 50

300

150

125

100

20.Source protection for AC input should be treated as if supplying a three phase transformer with a rating 1.4 times the UPS kVA rating, to allow for transformer magnetization inrush current.

21.The input breaker (CB1) has a trip rating of 150 amps AT for the 400, 480 and 600 volt input UPS and 320 amps AT for the 208 volt input UPS.

22.The bypass feed into this equipment utilizes either three or four wires. The rectifier feed into this equipment utilizes three wires. However, the phases must be symmetrical about ground (i.e., from a Wye source) for proper equipment operation. Failure to follow these instructions will void the product warranty.

23.The line-to-line unbalanced output capability of the UPS is limited by the full load per phase current values for AC output to critical load shown in Tables A through C. The recommended line-to-line load unbalance is 50% or less.

24.Table H lists the maximum rating for output circuit protection devices (circuit breakers).

Table H. Maximum Output Circuit Breaker Ratings

Balanced Power System

 

Output Voltage Rating

 

 

 

 

 

 

208V

 

400V

 

480V

 

 

 

 

 

 

 

 

 

Balanced Power 75

300

 

N/A

 

125

 

 

 

 

 

 

Balanced Power 62.5

225

 

125

 

100

Balanced Power 50

175

 

90

 

80

 

 

 

DESCRIPTION:

INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201261---1

 

SHEET: 6 of 11

 

 

 

 

 

 

REVISION: E

 

DATE:

093001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

 

 

 

A---7

164201261 Rev. F 111503

Page 139
Image 139
Powerware 5075 kVA Table G. Maximum Input Circuit Breaker Ratings, Table H. Maximum Output Circuit Breaker Ratings