Looking Inside the UPS
The Powerware BPIII HE is a continuous duty,
In this manual, the power required by your equipment is called the critical load. The UPS supplies the critical load with conditioned power that is synchronized with your utility power. Figure 17 shows the main elements of the UPS.
AC INPUT TO | DC INPUT | AC OUTPUT | AC INPUT |
| |||
RECTIFIER/ |
| TO CRITICAL | TO BYPASS |
CHARGER |
| LOAD |
|
| DC/DC |
|
|
| CONVERTER |
|
|
INPUT | POWER | PROCESSING | UNIT | |
ISOLATION | ||||
|
| OUTPUT | ||
TRANSFORMER |
|
| ||
|
| TRANSFORMER MAINTENANCE | ||
|
|
| ||
|
|
| ISOLATION | |
|
|
| SWITCH | |
|
|
| (MIS) | |
|
|
| OUTPUT | |
| RECTIFIER/ |
| CONTACTOR | |
| INVERTER | |||
| CHARGER |
|
| |
|
|
| MAINTENANCE | |
|
|
| BYPASS | |
|
| DIGITAL | BREAKER | |
|
| (MBP) | ||
|
| METERING | ||
|
|
|
INPUT |
FILTER |
STATIC
SWITCH
BYPASS
INPUT
BREAKER (BIB)
BYPASS
CONTACTOR
UPS CABINET
Figure 17. Main Elements of the UPS System
If utility power is interrupted or falls outside the parameters specified in the Product Specifications section of Chapter 16, the UPS uses a backup supply to sustain power to the critical load for a specified period of time or until the utility power returns. For extended power outages, the backup supply allows you to either transfer to an alternative power system (such as a generator) or shut down your critical load in an orderly manner.
The operation of the UPS system is described in greater detail in the following paragraphs. The Product Specifications section of Chapter 16 outlines the storage and operating specifications for the UPS.