Powerware 5075 kVA operation manual Path of Current Through the UPS in Battery Mode

Models: 5075 kVA

1 162
Download 162 pages 48.55 Kb
Page 51
Image 51

Battery Mode

The UPS transfers to Battery mode automatically if a utility power outage occurs, or if the utility power does not conform to specified parameters. In Battery mode, the battery, through the DC to DC voltage converter, provides emergency DC power that the inverter converts to AC power. When the UPS switches to Battery mode, the alarm indications depend on the cause and condition of the battery charge. The length of time the system can operate in Battery mode depends on loading and the battery supply capacity.

Figure 20 shows the path of electrical power through the UPS when operating in Battery mode.

Bypass

(BIB) Input

(closed)

BYPASS

(MBP)

(open)

OUTPUT

TRANSFORMER

RECTIFIER

Rectifier CB1

Input

Input

Isolation

Transformer

K4

INVERTER

DC/DC

CONVERTER

K3

Output

(MIS)

 

(closed)

(closed)

 

CB2

(closed)

Path of electrical power

BATTERY

Figure 20. Path of Current Through the UPS in Battery Mode

When the discharging battery voltage reaches the lower limit of UPS operation capability, the critical load transfers to Bypass mode if it is available. If Bypass input is not available, a “Shutdown Imminent” warning occurs. The warning time before critical load loss occurs is approximately 2 minutes, depending on battery capacity and the amount of loading.

If incoming power returns to within specified parameters, the UPS automatically returns to Normal mode and alarm indications clear. However, the process of returning to Normal mode is not instantaneous. The rectifier gradually draws increasing power from the incoming utility until Normal mode is achieved.

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

43

164201261 Rev. F 111503

Page 51
Image 51
Powerware 5075 kVA operation manual Path of Current Through the UPS in Battery Mode