Powerware 5075 kVA operation manual Mode, Rate

Models: 5075 kVA

1 162
Download 162 pages 48.55 Kb
Page 98
Image 98

Table 4 shows which options are available for each port. The sections that follow describe the configuration settings you can change.

Table 4. Options Available for Each Communication Port

Port 1

Port 2

Options

 

 

 

X

X

Terminal Mode

 

 

 

 

 

Calibration Mode

 

 

 

X

X

System Configuration

 

 

 

 

X

Computer Mode

 

 

 

X

 

Remote Monitor Mode

 

 

 

X

X

Baud rate of 300, 1200, 2400, 4800, 9600, or 19,200

 

 

 

X

X

Data size/stop bits of 8/1 or 8/2

 

 

 

 

X

Data size/stop bits of 7/1 or 7/2

 

 

 

X

X

Disabled handshaking

 

 

 

X

X

XON/XOFF handshaking

 

 

 

Mode

The operational mode of the port. Each communications port operates in one of the following modes:

Terminal mode

System events are logged immediately as they occur.

Calibration

Used only by service personnel.

System Config.

Allows you to set building alarms, battery tests, etc.

 

(Check with your Sales or Service Representative for availability.)

Computer

Provides a proprietary Binary Computer Mode (BCM) Interface.

Remote Monitor

Sends all system event information to an RMP, RIM, or

 

Supervisory Contact Module (SCM). Available for Port 1 only.

Port 1 and Port 2 cannot be in the same mode simultaneously; they must always be operating in different modes. The modes are described later in this chapter.

Rate

The baud rate of the equipment connected to this port. The baud rate determines the speed of data transferred between the UPS and the connected equipment. For Remote Monitor mode, the baud rate must be set to 300. All other modes should operate at the highest baud rate available with the connected equipment. 300 baud is not recommended for any mode except Remote Monitor.

You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200.

90

Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation

164291261 Rev. F 111503

Page 98
Image 98
Powerware 5075 kVA operation manual Mode, Rate