Powerware 5075 kVA operation manual Communications Panel

Models: 5075 kVA

1 162
Download 162 pages 48.55 Kb
Page 141
Image 141

Communications Panel

TB1

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

BLDG ALARM 1 BLDG ALARM 1 RTN BLDG ALARM 2 BLDG ALARM 2 RTN BLDG ALARM 3 BLDG ALARM 3 RTN BLDG ALARM 4 BLDG ALARM 4 RTN BLDG ALARM 5 BLDG ALARM 5 RTN BLDG ALARM 6

BLDG ALARM 6 RTN

TB2

1REMOTE EPO

2

REMOTE EPO RTN

RS485

3

 

 

4ON INV

5ON INV RTN

6ON BYPASS

7ON BYPASS RTN

8BATTERY CONTACTOR CLOSED

9BATTERY CONT RTN

10

RELAY 1 NO

 

11

RELAY 1 NC

 

12

ALARM RTN

 

13

RELAY 2 NO

RS232

 

14

RELAY 2 NC

15

NOTICE RTN

(Optional)

 

NOTE: Not all building alarms are available for customer use. For remote EPO, use an isolated normally open contactor switch (24VDC, 20ma minimum) connected at TB2-1 and TB2-2.

 

 

 

DESCRIPTION:

INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201261---1

 

SHEET: 8 of 11

 

 

 

 

 

 

REVISION: E

 

DATE:

093001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

 

 

 

A---9

164201261 Rev. F 111503

Page 141
Image 141
Powerware 5075 kVA operation manual Communications Panel