10.Refer to Table D for internal power cable terminations and Table E for external power cable terminations. Drawing 164201014---4 shows the location of these power cable terminals inside the UPS cabinets. Terminals E9 through E15, and E19 through E35 are UL and CSA rated at 90˚C. A hex key tool is required to attach wires to terminals.

Table D. Internal Power Cable Terminations

 

 

 

 

 

 

Tightening

Bolt or

 

 

 

 

 

 

Torque

Hex

 

 

Cable

 

 

Size of

N ---M

Size

Terminal Function

Terminal

Number

Function

 

Termination

(lb ---in )

(In.)

 

 

 

 

 

 

 

 

 

AC Input to UPS

E1

250

Phase ‘A’

1

--- 1 bolt mounting

9.0

(78)

1/4 bolt

Rectifier from

 

 

 

 

 

 

 

 

E2

251

Phase ‘B’

1

--- 1 bolt mounting

9.0

(78)

1/4 bolt

Environmental

 

 

 

 

 

 

 

 

Cabinet

E3

252

Phase ‘C’

1

--- 1 bolt mounting

9.0

(78)

1/4 bolt

 

 

 

 

 

 

 

 

 

AC Input to Bypass

E13

227

Phase ‘A’

1

--- #4---500 kcmil

42.4

(375)

3/8

Transformer from

 

 

 

 

 

 

 

 

E14

228

Phase ‘B’

1

--- #4---500 kcmil

42.4

(375)

3/8

Environmental

 

 

 

 

 

 

 

 

Cabinet

E15

229

Phase ‘C’

1

--- #4---500 kcmil

42.4

(375)

3/8

 

 

 

 

 

 

 

 

 

AC Output to

E9

237

Phase ‘A’

1

--- #6---350 kcmil

31.1

(275)

3/8

Environmental

 

 

 

 

 

 

 

 

E10

238

Phase ‘B’

1

--- #6---350 kcmil

31.1

(275)

3/8

Cabinet

 

 

 

 

 

 

 

 

 

E11

239

Phase ‘C’

1

--- #6---350 kcmil

31.1

(275)

3/8

 

 

 

 

 

 

 

 

 

 

E12

600

Neutral/

2

--- #4---500 kcmil

31.1

(275)

3/8

 

 

 

Gnd.

 

 

 

 

 

 

 

 

 

 

 

 

 

DC Input from

E4

205

Battery (+)

1

--- 1 bolt mounting

32 (277)

3/8 bolt

Environmental

 

 

 

 

 

 

 

 

E5

206

Battery (---)

1

--- 1 bolt mounting

32 (277)

3/8 bolt

Cabinet

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION:

INSTALLATION NOTES

 

 

 

 

 

 

DRAWING NO:

164201261---1

 

SHEET: 4 of 11

 

 

 

 

 

 

REVISION: B

 

DATE:

011500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operation

 

 

 

A---5

164201261 Rev. F 111503