PowerLogic™ PM5300 seriesChapter 15—MID Compliance

Lock-protected functions

Menu

Sub-menu

 

Lock-protected function

 

 

 

 

 

Global Resets

Meter Initialization (all)

 

Energies

Resets

 

Single Resets

Energy

 

 

Multi-Tariff

 

 

 

 

 

 

Setting up the PM5331/PM5341

You must configure all the lock-protected setup parameters before locking the meter.

When the meter is locked, those setup parameters cannot be edited.

Basic setup menu

See “Configuring the basic setup parameters” on page 34 to perform basic setup.

For MID compliance, the Power System must be set to one of the following settings:

3PH4W Wye Gnd (three-phase 4-wire wye grounded)

3PH3W Wye Ungnd (three-phase 3-wire wye ungrounded)

Advanced setup menu

See “Advanced setup” on page 41 to perform advanced setup.

You must use ION Setup to edit the device label.

Clock setup menu

See “Setting the clock” on page 41 to change the meter time using the display.

You can also use ION Setup to set or sync the meter time.

Tariff setup menu

See “Multi-tariff feature overview” on page 83 to configure the energy tariffs.

Passwords setup menu

See “Setting up the screen passwords” on page 39 to change the meter screen passwords.

Initializing the meter

Initializing the meter clears the meter’s logged data, counters and timers. It is common practice to initialize the meter after its configuration is complete, before adding it to an energy management system.

1.After configuring all the meter setup parameters, navigate through the different meter display screens and make sure the displayed data is valid.

2.See “Meter resets” on page 99 for instructions on clearing the meter’s recorded logged data, counters and timers.

3.Select Meter Initialization to clear all recorded data.

© 2014 Schneider Electric All Rights Reserved

111

Page 111
Image 111
Schneider Electric PM5300 manual Setting up the PM5331/PM5341, Initializing the meter