PowerLogic™ PM5300 series user guide

Chapter 4—Front panel display and meter setup

 

 

Input / output setup

Demand setup

Related topics

See “Setting up the alarm / energy pulsing LED” on page 42 for details on setting up the LED for alarms.

The meter’s input/output (I/O) ports extend the capabilities of the meter. The I/O ports can be configured using the front panel or ION Setup.

Related topics

See “Input / Output” on page 49 for a comprehensive description and setup instructions using the front panel.

See “Technical Specifications” on page 15 for electrical characteristics and limits of meter’s I/O ports.

Demand is a measure of average consumption over a fixed time interval.

Use the Demand setup screens to define power demand, current demand or input metering demand.

Demand setup menu tree

Maint

Reset

Meter

Basic

Advan

Dmd

Tariff

 

Setup

Comm

 

 

 

 

 

 

Alarm

 

 

 

 

 

 

I/O

 

 

 

 

 

 

HMI

 

 

 

 

 

 

Clock

 

 

 

 

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0000”), then press OK.

3.Navigate to Meter > Dmd.

4.Move the cursor to select Power Demand or Current Demand.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

6.Modify the parameter as required, then press OK.

7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

Power or current demand setup parameters

Parameter

Values

Description

 

 

 

 

Timed Sliding Block

 

 

Timed Block

 

 

Timed Rolling Block

 

 

Cmd Sync Block

 

Method

Cmd Sync Roll Block

See “Demand” on page 79 for details.

Clock Sync Block

 

 

 

Clock Sync Roll Block

 

 

Input Sync Block

 

 

Input Sync Roll Block

 

 

Thermal

 

 

 

 

Interval (min)

0 - 60

Set the demand interval, in minutes.

 

 

 

© 2014 Schneider Electric All Rights Reserved

43

Page 43
Image 43