PowerLogic™ PM5300 series user guide

Chapter 3—Hardware Reference

Frequency

 

 

Real, reactive, and apparent power (Total and per phase)

Signed, Four Quadrant

True Power Factor (Total and per phase)

Signed, Four Quadrant

Displacement PF (Total and per phase)

Signed, Four Quadrant

% Unbalanced I, V L-N, V L-L

 

 

Energy Values*

Accumulated Active, Reactive and Apparent Energy

Received/Delivered; Net and absolute

Demand Values*

Current average

Present, Last, Predicted, Peak, and Peak

Date Time

 

Active power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Reactive power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Apparent power

Present, Last, Predicted, Peak, and Peak

Date Time

 

Demand calculation (Sliding, fixed and rolling block, thermal

methods)

 

Synchronization of the measurement window to input,

communication command or internal clock

 

Settable Demand intervals

 

 

Other Measurements*

I/O timer

Operating timer

Load timer

Alarm counters and alarm logs

Power Quality Measurements

THD, thd (Total Harmonic Distortion) I, V L-N, V L-L per phase

I, V L-N, V L-L

TDD (Total Demand Distortion)

 

 

Individual harmonics (odds)

31st

Data Recording

 

 

 

Min/max of instantaneous values, plus phase identification*

 

 

Alarms with 1s timestamping*

 

 

 

Up to two fixed parameters (e.g., kWh and

Data logging

kVAh) with configurable interval and duration

(e.g., 2 parameters for 60 days at 15 minutes

 

 

interval)

Memory capacity

256 kB

Min/max log

 

 

Maintenance, alarm and event logs

 

 

Inputs/Outputs/Relays

Digital inputs Digital outputs Form A Relay outputs

Timestamp resolution in seconds

Whetting voltage

2

2

2

1

NOTE: *Stored in non-volatile memory

14

© 2014 Schneider Electric All Rights Reserved

Page 14
Image 14
Schneider Electric PM5300 Energy Values, Demand Values, Other Measurements, Power Quality Measurements, Data Recording