Schneider Electric PM5300 manual Setting Up 1-Second Alarms

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 68
Image 68

PowerLogic™ PM5300 series user guide

Chapter 7—Alarms

Setting Up 1-Second Alarms (continued)

17.Press to select Priority, then press Edit.

18.Press + and - to scroll through priority options None, High, Medium, or Low.

NOTE: See “Alarm Priorities” on page 66 for more information.

19.Press OK to set the priority.

20.Press to select Select Digital Output, then press Edit.

21.Press + and - to scroll through the list of digital outputs to associate with the alarm.

22.Press OK to select a digital output to be associated with the selected alarm.

23.If the selected digital output already has an association that will be lost by making the new selection, a confirmation screen appears.

Press Yes to accept the changes and return to the previous screen.

Press No to keep the existing configuration in use and return to the previous screen.

24.Press to save all alarm selections and return to the previous screen.

25.Press to save all 1-second alarm selections.

NOTE: The Over Demand alarms are applicable for systems in which the energy is delivered to the customer only.

68

© 2014 Schneider Electric All Rights Reserved

Page 68
Image 68
Schneider Electric PM5300 manual Setting Up 1-Second Alarms