Schneider Electric PM5300 manual Hz F, Unbal, MnMx, Alarm

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 47
Image 47

PowerLogic™ PM5300 series user guide

Chapter 5—Viewing Meter Data

 

 

PF

True

Disp

Per phase and total true power factor values and sign.

Per phase and total displacement power factor values and sign.

Hz [F]

Frequency (Freq), average voltage and current (Vavg, Iavg) and power factor (PF) values.

THD

THD

THD (ratio of harmonic content to the fundamental) for current,

 

Amps [I], V L-L [U], V L-N [V]

line-to-line voltage, and line-to-neutral voltage.

 

 

thd

thd (ratio of harmonic content to the rms value of total harmonic

 

 

content) for current, line-to-line voltage, and line-to-neutral

 

Amps [I], V L-L [U], V L-N [V]

 

voltage.

 

 

 

Related topics

See “Power quality” on page 89.

Unbal

Percent unbalance readings for line-to-line voltage (V L-L [U]), line-to-neutral voltage (V L-N [V]) and current (Amps [I]).

MnMx

MnMx

Summary of maximum values for line-to-line voltage, line-to-

neutral voltage, phase current and total power.

 

 

 

 

 

 

 

 

 

 

Amps [I]

Minimum and maximum values for phase current.

 

 

 

 

 

 

Volts

Minimum and maximum values for line-to-line voltage and line-

 

 

V L-L, V L-N

to-neutral voltage.

 

 

 

 

 

Power

Minimum and maximum values for active, reactive, and apparent

 

 

Active, Reac, Apr

power.

 

 

 

 

 

PF

Minimum and maximum values for true and displacement PF and

 

 

True, Disp

PF sign.

 

 

 

 

 

Hz

Minimum and maximum values for frequency.

 

 

 

 

 

THD

Minimum and maximum values for total harmonic distortion (THD

 

 

THD, thd

or thd).

 

 

 

 

 

 

 

 

Amps, V L-L, V L-N

THD or thd minimum and maximum values for phase or neutral

 

 

 

current, line-to-line voltage and line-to-neutral voltage.

 

 

 

 

 

Unbal

Minimum and maximum values for current unbalance, line-to-line

 

 

Amps, V L-L, V L-N

voltage unbalance and line-to-neutral voltage unbalance..

 

 

 

 

 

Alarm

Active, Hist, Count, Unack

Lists all active alarms, past alarms (Hist), the total number each standard alarm has been tripped (Count), and all unacknowledged alarms.

Related topics

See “Alarms” on page 63.

I/O

DOut

S In

Relay

Current status (on or off) of the selected digital output, status input or relay. Counter shows the total number of times an off-to- on change of state is detected. Timer shows the total time (in seconds) that a digital output, status input or relay is in the on state.

Related topics

See “Input / Output” on page 49.

© 2014 Schneider Electric All Rights Reserved

47

Page 47
Image 47
Schneider Electric PM5300 manual Hz F, Unbal, MnMx, Alarm