Schneider Electric PM5300 Setting up Ethernet communications, Communications setup parameters

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 37
Image 37

PowerLogic™ PM5300 series user guideChapter 4—Front panel display and meter setup

Communications setup parameters

Parameter

Values

Description

 

 

 

 

 

The communications format used to transmit data. The

Protocol

Modbus

protocol must be the same for all devices in a

 

 

communications loop.

 

 

Set the address for this device. The address must be

Address

1 to 247

unique for each device in a communications loop. For

 

 

Jbus protocol, set the device ID to 255.

 

 

Select the speed for data transmission. The baud rate

Baud Rate

9600, 19200, 38400

must be the same for all devices in a communications

 

 

loop.

 

 

Select None if the parity bit is not used. The parity

Parity

Even, Odd, None

setting must be the same for all devices in a

 

 

communications loop.

7. Press to exit. Press Yes to save your changes.

Setting up Ethernet communications

The Ethernet Port setup screen allows you to assign the meter a unique IP address so you can use software to access the meter’s data or configure the meter remotely through the Ethernet port. Before configuring the Ethernet parameters, make sure you obtain your meter’s IP address information from your network administrator or IT department.

Ethernet communications setup menu tree

Maint

Reset

Setup

Meter

Comm

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0000”), then press OK.

3.Press Comm.

4.Move the cursor to point to the parameter you want to modify, then press Edit.

5.Modify the parameter as required, then press OK.

6.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

© 2014 Schneider Electric All Rights Reserved

37

Page 37
Image 37
Schneider Electric PM5300 manual Setting up Ethernet communications, Communications setup parameters