Schneider Electric PM5300 manual Configuring digital outputs using the front panel

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 54
Image 54

Chapter 6—Input / Output

PowerLogic™ PM5300 series user guide

 

 

Digital output setup parameters available through ION Setup (continued)

Parameter

 

Values

Description

 

 

 

 

 

1.

Over Current, Ph;

 

 

2.

Under Current, Ph;

 

 

3.

Over Current, N;

 

 

4.

Over Current Gnd;

 

 

5.

Over Voltage, L-L;

 

 

6.

Under Voltage, L-L;

 

 

7.

Over Voltage, L-N;

 

 

8.

Under Voltage L-N;

 

 

9.

Over kW;

 

 

10.

Over kVAR;

 

 

11.

Over kVA;

 

 

12.

Lead PF, True;

 

 

13.

Lag PF, True;

 

 

14.

Lead PF, Disp;

 

 

15.

Lag PF, Disp;

 

 

16.

Over kW Dmd, Pres;

 

 

17.

Over kW Dmd, Last;

Applies when Control Mode is set to Alarm. Select

Select Alarms

18.

Over kW Dmd, Pred;

one or more alarms to monitor.

 

19.

Over kVAR Dmd,Pres;

 

 

 

20.

Over kVAR Dmd,Last;

 

 

21.

Over kVAR Dmd,Pred;

 

 

22.

Over kVA Dmd, Pres;

 

 

23.

Over kVA Dmd, Last;

 

 

24.

Over kVA Dmd, Pred;

 

 

25.

Over Frequency;

 

 

26.

Under Frequency;

 

 

27.

Over Voltage Unbal;

 

 

28.

Over Voltage THD;

 

 

29.

Phase Loss;

 

 

30.

Meter Powerup;

 

 

31.

Meter Reset;

 

 

32.

Meter Diagnostic;

 

 

33.

Phase Reversal;

 

 

34.

Digital Alarm S1;

 

 

35.

Digital Alarm S2;

 

 

 

 

 

 

 

 

This field displays additional information if the digital

Associations

 

output is already associated with another meter

 

 

 

function.

Configuring digital outputs using the front panel

You can use the front panel to configure the digital outputs.

Digital output setup menu tree

Maint

Reset

Setup

Meter

Comm

Alarm

I/O

HMI

Clock

LED

SIn D Out Relay

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0000”), then press OK.

3.Navigate to I/O > D Out.

54

© 2014 Schneider Electric All Rights Reserved

Page 54
Image 54
Schneider Electric PM5300 manual Configuring digital outputs using the front panel, Digital output setup menu tree