Chapter | PowerLogic™ PM5300 series user guide |
|
|
3.Navigate to Meter > Advan.
4.Move the cursor to point to the parameter you want to modify, then press Edit.
5.Modify the parameter as required, then press OK.
6.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.
Advanced setup parameters
Parameter | Values | Description | |
|
|
| |
|
| This label identifies the device, e.g., “Power | |
Label | Meter”. You cannot use the front panel to edit | ||
this parameter. Use ION Setup to change the | |||
|
| ||
|
| device label. | |
|
|
| |
|
| Specifies the minimum average current at the | |
Load Timer Setpt (A) | 0 - 99999 | load before the timer starts. The meter begins | |
counting the operating time whenever the | |||
|
| readings are equal to or above this average | |
|
| current threshold. | |
|
| Specifies the minimum peak current demand | |
|
| at the load for inclusion in total demand | |
|
| distortion (TDD) calculations. If the load | |
Pk I dmd for TDD (A) | 0 - 99999 | current is below the minimum peak current | |
demand threshold, the meter does not use the | |||
|
| readings to calculate TDD. Set this to “0” | |
|
| (zero) if you want the power meter to use the | |
|
| metered peak current demand for this | |
|
| calculation. |
7. Press Yes to save your changes.
Related topics
•See“Total Harmonic Distortion and Total Demand Distortion” on page 89 for details on how the meter calculates TDD.
Setting up the alarm / energy pulsing LED
The LED setup screen allows you to configure the alarm / energy pulsing LED for alarming or energy pulsing application.
Alarm / energy pulsing LED settings menu tree
Maint | Reset | Meter |
|
| Setup | Comm | LED |
|
| Alarm | S In |
|
| I/O | D Out |
|
| HMI | Relay |
|
| Clock |
|
1.Navigate to Maint > Setup.
2.Enter the setup password (default is “0000”), then press OK.
3.Navigate to I/O > LED.
4.Press Edit.
5. Press |
| or |
| to modify the parameter as required, then press OK. | |||
|
| ||||||
LED setup parameter |
| ||||||
|
|
|
|
|
|
|
|
| Parameter |
| Values | Description | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Off disables the LED. |
| Mode |
| Off, Alarm, Energy | Alarm sets the LED for alarm notification. | |||
|
|
|
|
|
|
| Energy sets the LED for energy pulsing. |
6. Press
to exit. Press Yes to save your changes.
42 | © 2014 Schneider Electric All Rights Reserved |