Schneider Electric PM5300 Data Logs, Description Number of Registers Data Type Register Number

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 75
Image 75

PowerLogic™ PM5300 series user guide

Chapter 8—Data Logs

Chapter 8—Data Logs

This chapter briefly describes the following logs of the power and energy meter:

Alarm Log

User-defined data log

Logs are files stored in the non-volatile memory of the power and energy meter and are referred to as “on-board logs”.

Data Logs

The PM5300 series records and stores readings at regularly scheduled intervals in one independent data log. This log will be in disabled state from the factory. You can set up the data log to store the following information.

Time Interval: 15, 30, 60 minutes

First-in-first-out (FIFO) or Fill and Hold

Values logged - up to 2 registers along with data and time of each log entry

The registers list for configuring the data logs

Description

Number of Registers

Data Type

Register Number

Active energy delivered

4

Integer

3204

Active energy received

4

Integer

3208

Reactive energy delivered

4

Integer

3220

Reactive energy received

4

Integer

3224

Apparent energy delivered

4

Integer

3236

Apparent energy received

4

Integer

3240

Status input 1 counter

1

Integer

8915

Status input 2 counter

1

Integer

8919

© 2014 Schneider Electric All Rights Reserved