PowerLogic™ PM5300 series user guide

Chapter 6—Input / Output

 

 

Configuring relay outputs using the front panel

You can use the front panel to configure the relay outputs.

Relay output setup menu tree

Maint

Reset

Setup

Meter

Comm

Alarm

I/O

HMI

Clock

LED

SIn D Out Relay

1.Navigate to Maint > Setup.

2.Enter the setup password (default is “0”), then press OK.

3.Navigate to I/O > Relay.

4.Move the cursor to point to the relay output you want to set up, then press Edit.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

NOTE: If Edit is not displayed, it means the parameter is either read-only or can only be modified through software.

6.Modify the parameter as required, then press OK.

7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

8.Press to exit. Press Yes to save your changes.

Relay output setup parameters available through the front panel

Parameter

Values

Description

 

 

 

 

 

This can be modified only through software. Use this

Label

-----

field to change the default label and assign a

 

 

descriptive name to this relay output.

 

 

This displays how the relay output functions.

 

 

• External: the relay output is controlled remotely

Control Mode

External, Alarm

either through software or by a PLC using

commands sent through communications.

 

 

• Alarm: the relay output is associated with the

 

 

alarm system. The meter sends a pulse to the

 

 

relay output port when the alarm is triggered.

 

 

• Normal: this applies when control mode is set to

 

 

External or Alarm. The relay output remains in

 

 

the ON state until an OFF command is sent by

 

 

the computer or PLC.

 

 

• Timed: the relay output remains ON for the period

 

 

defined by the On Time setup register.

Behavior Mode

Normal, Timed, Coil Hold

• Coil Hold: this applies when control mode is set to

External or Alarm. For a unary alarm that is

 

 

associated with a relay output, you must set

 

 

Behavior Mode to Coil Hold. The output turns on

 

 

when the “energize” command is received and

 

 

turns off when the “coil hold release” command is

 

 

received. In the event of a control power loss, the

 

 

output remembers and returns to the state it was

 

 

in when control power was lost.

© 2014 Schneider Electric All Rights Reserved