PowerLogic™ PM5300 series user guide

Chapter 3—Hardware Reference

Technical Specifications

Electrical Characteristics

Type of measurement: True rms on three-phase (3P, 3P + N), zero blind

Measurement accuracy

64 samples per cycle

IEC 61557-12 1

PMD/[SDSS]/K70/0.5

Active Energy 2

Class 0.5S as per IEC 62053-22

Reactive Energy 2

Class 2S as per IEC 62053-23

Active Power

Class 0.5 as per IEC 61557-12 1

Reactive Power

Class 2 as per IEC 61557-12 1

Apparent Power

Class 0.5 as per IEC 61557-12 1

Current, Phase

Class 0.5 as per IEC 61557-12 1

Voltage, L-N

Class 0.5 as per IEC 61557-12 1

Frequency

Class 0.05 as per IEC 61557-12 1

Power Factor

Class 0.5 as per IEC 61557-12 1

Voltage Harmonics

Class 5 as per IEC 61557-12 1

Voltage THD/thd

Class 5 as per IEC 61557-12 1

Current Harmonics

Class 5 as per IEC 61557-12 1

Current THD/thd

Class 5 as per IEC 61557-12 1

MID Directive (2004/22/EC)

Annex B and Annex D (PM5331 and PM5341)

Class C

 

Input-voltage (up to 1.0 MV AC max, with voltage transformer)

 

UL: 20-347 V L-N/35-600 V L-L

Nominal Measured Voltage range

IEC: 20-400 V L-N/35-690 V L-L

 

(absolute range 35 V L-L to 760 V L-L)

Impedance

5 M

F nom

50/60 Hz

Input-current (configurable for 1 or 5 A secondary CTs)

 

I nom

5 A

Measured Amps with over range and Crest Factor

Starting current: 5mA

Operating range: 50mA to 8.5A

 

Withstand

Continuous 20 A,10s/hr 50 A, 1s/hr 500 A

Impedance

< 0.3 m

F nom

50/60 Hz

Burden

<0.026VA at 8.5A

Frequency measurement

 

Measurement range

45 to 65 Hz

AC control power

 

Operating range

100 - 277 V AC L-N / 415 V L-L +/-10%

CAT III 300V class per IEC 61010

 

Burden

<5 W,11 VA at 415V L-L

Frequency

45 to 65 Hz

 

80 mS typical at 120V AC and maximum burden.

Ride-through time

100 mS typical at 230 V AC and maximum burden

 

100 mS typical at 415 V AC and maximum burden

DC control power

 

Operating range

125-250 V DC ±20%

Burden

<4 W at 250 V DC

Ride-through time

50 mS typical at 125 V DC and maximum burden

Outputs

 

Mechanical

 

Max output frequency

0.5 Hz maximum (1 second ON /

1 second OFF - minimum times)

 

 

250 V AC at 8.0 Amps, 25 k cycles, resistive

Switching current

30 V DC at 2.0 Amps, 75 k cycles, resistive

 

30 V DC at 5.0 Amps,12.5 k cycles, resistive

Isolation

2.5 kV rms

Digital outputs

 

Max load voltage

40 V DC

Max load current

20 mA

On Resistance

50 max

© 2014 Schneider Electric All Rights Reserved

15

Page 15
Image 15