Schneider Electric PM5300 manual On Time s This defines the pulse width on time in seconds

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 55
Image 55

PowerLogic™ PM5300 series user guide

Chapter 6—Input / Output

 

 

4.Move the cursor to point to the digital output you want to set up, then press Edit.

5.Move the cursor to point to the parameter you want to modify, then press Edit.

NOTE: If Edit is not displayed, it means the parameter is either read-only or can only be modified through software.

6.Modify the parameter as required, then press OK.

7.Move the cursor to point to the next parameter you want to modify, press Edit, make your changes, then press OK.

8.Press to exit. Press Yes to save your changes.

Digital output setup parameters available through the front panel

Parameter

Values

Description

 

 

 

 

 

This can be modified only through software. Use this

Label

-----

field to change the default label and assign a

 

 

descriptive name to this digital output.

 

 

This displays how the digital output functions.

 

 

• External: the digital output is controlled remotely

 

 

either through software or by a PLC using

 

 

commands sent through communications.

Control Mode

External, Demand Sync,

• Demand Sync: the digital output is associated

Alarm

with one of the demand systems. The meter

 

 

sends a pulse to the digital output port at the end

 

 

of every demand interval.

 

 

• Alarm: the digital output is associated with the

 

 

alarm system. The meter sends a pulse to the

 

 

digital output port when the alarm is triggered.

 

 

• Normal: this applies when control mode is set to

 

 

External or Alarm. The digital output remains in

 

 

the ON state until an OFF command is sent by

 

 

the computer or PLC.

 

 

• Timed: the digital output remains ON for the

 

 

period defined by the On Time setup register.

Behavior Mode

Normal, Timed, Coil Hold

• Coil Hold: this applies when control mode is set to

External or Alarm. For a unary alarm that is

 

 

associated with a digital output, you must set

 

 

Behavior Mode to Coil Hold. The output turns on

 

 

when the “energize” command is received and

 

 

turns off when the “coil hold release” command is

 

 

received. In the event of a control power loss, the

 

 

output remembers and returns to the state it was

 

 

in when control power was lost.

On Time (s)

0 to 9999

This defines the pulse width (ON time) in seconds.

 

 

 

© 2014 Schneider Electric All Rights Reserved

55