PowerLogic™ PM5300 series user guide | Chapter |
| from 1 to 9,999,999 pulses per k_h (k_h = kWh, | |
Meter constant | kVARh or kVAh depending on the energy | |
| parameter selected) | |
Pulse width for Digital Output | 50% duty cycle | |
Pulse frequency for Digital Output | 25 Hz max. | |
Leakage current | 0.03 micro Amps | |
Isolation | 5 kV rms | |
Optical outputs |
| |
Pulse width (LED) | 200 μs | |
Pulse frequency | 50 Hz. max. | |
Meter constant | from 1 to 9,999,999 pulses per k_h | |
Status Inputs |
| |
ON Voltage | 18.5 to 36 V DC | |
OFF Voltage | 0 to 4 V DC | |
Input Resistance | 110 k Ω | |
Maximum Frequency | 2 Hz (T ON min = T OFF min = 250 ms) | |
Response Time | 20 ms | |
Opto Isolation | 5 kV rms | |
Whetting output | 24 V DC/ 8mA max | |
Input Burden | 2 mA @ 24 V DC | |
Mechanical Characteristics |
| |
|
| |
Product weight | 430 g | |
IP degree of protection (IEC 60529) | IP52 front display, IP30 meter body | |
Dimensions W x H x D [protrusion from cabinet] | 96 x 96 x 72mm (depth of meter from housing | |
mounting flange) [13mm] | ||
| ||
Mounting position | Vertical | |
Panel thickness | 6 mm maximum | |
Environmental Characteristics |
| |
|
| |
Operating temperature |
| |
Meter | ||
Display (Display functions to | ||
performance) | ||
| ||
Storage temp. | ||
Humidity range | 5 to 95 % RH at 50 °C | |
Pollution degree | 2 | |
Altitude | 2000 m CAT III / 3000 m CAT II | |
For indoor use only |
| |
Electromagnetic Compatibility 3 |
| |
Electrostatic discharge | IEC | |
Immunity to radiated fields | IEC | |
Immunity to fast transients | IEC | |
Immunity to surge | IEC | |
Conducted immunity 150kHz to 80MHz | IEC | |
Immunity to magnetic fields | IEC | |
Immunity to voltage dips | IEC | |
Radiated emissions | FCC part 15, EN 55022 Class B | |
Conducted emissions | FCC part 15, EN 55022 Class B | |
Safety |
| |
|
| |
Europe | CE, as per IEC | |
11 & | ||
U.S. and Canada | cULus as per | |
| ||
Measurement category (Voltage and Current inputs) | CAT III up to 400 V | |
Dielectric | As per IEC/UL | |
Protective Class | II, Double insulated for user accessible parts | |
Communication |
| |
|
| |
| ||
Odd, None, 1 stop bit if parity Odd or Even, 2 stop | ||
| bits if None; (Optional) | |
Ethernet port: 10/100 Mbps; Modbus TCP/IP | 1 (Optional) | |
Firmware and language file update | Meter firmware update via the communication | |
ports | ||
|
16 | © 2014 Schneider Electric All Rights Reserved |