Schneider Electric PM5300 manual Mechanical Characteristics, Environmental Characteristics, Safety

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 16
Image 16

PowerLogic™ PM5300 series user guide

Chapter 3—Hardware Reference

 

from 1 to 9,999,999 pulses per k_h (k_h = kWh,

Meter constant

kVARh or kVAh depending on the energy

 

parameter selected)

Pulse width for Digital Output

50% duty cycle

Pulse frequency for Digital Output

25 Hz max.

Leakage current

0.03 micro Amps

Isolation

5 kV rms

Optical outputs

 

Pulse width (LED)

200 μs

Pulse frequency

50 Hz. max.

Meter constant

from 1 to 9,999,999 pulses per k_h

Status Inputs

 

ON Voltage

18.5 to 36 V DC

OFF Voltage

0 to 4 V DC

Input Resistance

110 k Ω

Maximum Frequency

2 Hz (T ON min = T OFF min = 250 ms)

Response Time

20 ms

Opto Isolation

5 kV rms

Whetting output

24 V DC/ 8mA max

Input Burden

2 mA @ 24 V DC

Mechanical Characteristics

 

 

 

Product weight

430 g

IP degree of protection (IEC 60529)

IP52 front display, IP30 meter body

Dimensions W x H x D [protrusion from cabinet]

96 x 96 x 72mm (depth of meter from housing

mounting flange) [13mm]

 

Mounting position

Vertical

Panel thickness

6 mm maximum

Environmental Characteristics

 

 

 

Operating temperature

 

Meter

-25 °C to +70 °C

Display (Display functions to -25º with reduced

-25 °C to +70 °C

performance)

 

Storage temp.

-40 °C to +85 °C

Humidity range

5 to 95 % RH at 50 °C (non-condensing)

Pollution degree

2

Altitude

2000 m CAT III / 3000 m CAT II

For indoor use only

 

Electromagnetic Compatibility 3

 

Electrostatic discharge

IEC 61000-4-2

Immunity to radiated fields

IEC 61000-4-3

Immunity to fast transients

IEC 61000-4-4

Immunity to surge

IEC 61000-4-5

Conducted immunity 150kHz to 80MHz

IEC 61000-4-6

Immunity to magnetic fields

IEC 61000-4-8

Immunity to voltage dips

IEC 61000-4-11

Radiated emissions

FCC part 15, EN 55022 Class B

Conducted emissions

FCC part 15, EN 55022 Class B

Safety

 

 

 

Europe

CE, as per IEC 61010-1 (3rd Edition), IEC 62052-

11 & IEC61557-121

U.S. and Canada

cULus as per UL61010-1 (3rd Edition)

CAN/CSA-C22.2 No. 61010-1 (3rd Edition)

 

Measurement category (Voltage and Current inputs)

CAT III up to 400 V L-N / 690 V L-L

Dielectric

As per IEC/UL 61010-1 (3rd Edition)

Protective Class

II, Double insulated for user accessible parts

Communication

 

 

 

 

2-Wire, 9600,19200 or 38400 baud, Parity - Even,

RS-485 port Modbus RTU, Modbus ASCII (7 or 8 bit), JBUS

Odd, None, 1 stop bit if parity Odd or Even, 2 stop

 

bits if None; (Optional)

Ethernet port: 10/100 Mbps; Modbus TCP/IP

1 (Optional)

Firmware and language file update

Meter firmware update via the communication

ports

 

16