Chapter 6—Input / Output

PowerLogic™ PM5300 series user guide

 

 

Related topics

See “Technical Specifications” on page 15 for electrical characteristics and limits for the status inputs.

Status input setup

The status input ports (S1 and S2) can be configured using the front panel or

ION Setup software.

NOTE: It is recommended you use ION Setup to configure the status inputs, as setup parameters that require text entry can only be modified using ION Setup.

Configuring status inputs using ION Setup

You can use ION Setup to configure the status inputs.

1.Start ION Setup.

2.Connect to your meter.

3.Navigate to I/O configuration > I/O Setup.

4.Select a status input to configure and click Edit. The setup screen for that status input is displayed.

5.Enter a descriptive name for the status input’s Label.

6.Configure the other setup parameters as required.

7.Click Send to save your changes.

Status input setup parameters available through ION Setup

Parameter

Values

Description

 

 

 

Label

Use this field to change the default label and assign a

descriptive name to this status input.

 

 

 

 

This field displays how the status input functions.

 

 

• Normal: the status input is not associated with

 

 

another meter function. The meter counts and

 

 

records the number of incoming pulses normally.

 

 

• Demand Sync: the status input is associated with

Control Mode

Normal, Demand Sync, Input

one of the input sync demand functions. The meter

Metering

uses the incoming pulse to synchronize its demand

 

 

period with the external source.

 

 

• Input Metering: the status input is associated with

 

 

one of the input metering channels. The meter

 

 

counts and records the number of incoming pulses

 

 

and related consumption data associated with the

 

 

pulses.

 

 

Debounce is the time delay that compensates for

Debounce

0 to 9999

mechanical contact bounce. Use this field to set how

long (in milliseconds) the external signal must remain in

 

 

 

 

a certain state to be considered a valid state change.

 

 

 

Associations

This field displays additional information if the status

input is already associated with another meter function.

 

 

50