PowerLogic™ PM5300 series user guide

Chapter 6—Input / Output

 

 

Relay output applications

Relay outputs are typically used in switching applications, for example, to provide on/off control signals for switching capacitor banks, generators, and other external devices and equipment.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E in the USA or applicable local standards.

Turn off all power supplying this device before working on it.

Always use a properly rated voltage sensing device to confirm that all power is off.

Do not exceed the device’s ratings for maximum limits.

Do not use this device for critical control or protection applications where human or equipment safety relies on the operation of the control circuit.

Failure to follow these instructions will result in death or serious injury.

NOTE: Be aware that an unexpected change of state of the relay outputs may result when the supply power to the meter is interrupted or after a meter firmware upgrade.

Relay output setup

The relay output ports (Relay 1 and Relay 2) can be configured using the front panel or

ION Setup.

NOTE: It is recommended you use ION Setup to configure the relay outputs, as setup parameters that require text entry can only be modified using software.

Configuring relay outputs using ION Setup

You can use ION Setup to configure the relay outputs (Relay 1 and Relay 2).

1.Start ION Setup.

2.Connect to your meter

3.Navigate to I/O configuration > I/O Setup.

4.Select a relay output to configure and click Edit. The setup screen for that relay output is displayed.

5.Enter a descriptive name for the relay output’s Label.

6.Configure the other setup parameters as required.

7.Click Send to save your changes.

Relay output setup parameters available through ION Setup

Parameter

Values

Description

 

 

 

Label

Use this field to change the default label and assign a

descriptive name to this relay output.

 

 

 

 

This field displays how the relay output functions.

 

 

• External: the relay output is controlled remotely

Control Mode

External, Alarm

either through software or by a PLC using

commands sent through communications.

 

 

• Alarm: the relay output is associated with the

 

 

alarm system. The meter sends a pulse to the

 

 

relay output port when the alarm is triggered.

© 2014 Schneider Electric All Rights Reserved

57

Page 57
Image 57