Schneider Electric PM5300 manual Setting Up Digital Alarms

Models: PM5300

1 120
Download 120 pages 18.02 Kb
Page 70
Image 70

PowerLogic™ PM5300 series user guide

Chapter 7—Alarms

Setting Up Digital Alarms

To set up digital alarms:

1.Press Dig. The digital alarm Select screen appears.

2.Press and to scroll through the list of digital alarms.

3.Press Edit to select an alarm to be configured.

4.Press Edit to select Pickup Setpoint, then press Edit.

5.Press + and - to scroll between On and Off.

6.Press OK to enter the pickup setpoint.

7.Press to select Pickup Time Delay, then press Edit.

NOTE: If the selected status input mode is Demand Sync or Input Metering, a confirmation screen appears warning that if an alarm is enabled for this status input, the existing association will be broken.

8.Press + to increment the active digit through the numerals 0-9.

NOTE: Units for time delays are set in seconds.

9.Press to enter the selected value for the active digit and move to the next digit to the left.

10.Continue until all values are selected, then press OK to enter the pickup time delay.

11.Press to select Dropout Time Delay, then press Edit.

12.Follow Steps 8 to 11 for the dropout time delay.

70

© 2014 Schneider Electric All Rights Reserved

Page 70
Image 70
Schneider Electric PM5300 manual Setting Up Digital Alarms