PowerLogic™ PM5300 series user guide | Chapter |
|
|
Configuring tariffs using the front panel
This section explains how to use the front panel to set up tariffs.
Tariff setup menu tree
Maint | Reset | Meter | Basic | Advan | Dmd | Tariff |
| Setup | Comm |
|
|
|
|
|
| Alarm |
|
|
|
|
|
| I/O |
|
|
|
|
|
| HMI |
|
|
|
|
|
| Clock |
|
|
|
|
You can change the tariff mode using the front panel.
When the meter is set to command mode for tariffs, the active tariff is controlled by Modbus commands sent from your energy management system or other Modbus master.
Related topics
•Search PM5300 Modbus register list at
Configuring time of day mode tariffs using the front panel
When the meter is set to time of day for tariffs, the active tariff is determined by the day type, the start and end times, and the start and end dates. The time of day tariff is not a calendar; the meter does not calculate the corresponding day of the week to a specific date, but February 29th is considered a valid date if you are programming the meter during a leap year.
When you enter tariff times using the front panel, be aware that the displayed minute value includes the entire minute. For example, an end time of 01:15 includes the time from 01:15:00 through 01:15:59. To create a tariff period that starts right after this, you must set the next tariff’s start time to 01:16. Although it may appear that there is a gap between these tariffs, there is not.
1.Navigate to Maint > Setup.
2.Enter the setup password (default is “0”), then press OK.
3.Navigate to Meter > Tariff.
4.With the cursor pointing to Mode, press Edit.
5. Press or to change the setting to Time of Day, then press OK.
6.Move the cursor to point to the tariff (Tariff 1 to Tariff 4) you want to modify, then press Edit.
Time of day mode tariff setup
Parameter | Values | Description | |
|
|
| |
| Everyday, Weekday, Weekend, | Select which day the tariff is active. Only | |
| tariffs that are Everyday can have a tariff that | ||
Day Type | Monday, Tuesday, Wednesday, | ||
includes midnight (for instance, from 11pm | |||
| Thursday, Friday, Saturday or Sunday | ||
| to 2am). | ||
|
| ||
|
|
| |
|
| Set the time when the tariff period starts, | |
Start Time | 0000 to 2359 | using the 24 hour clock format (00:00 to | |
23:59). The Start Time cannot equal the End | |||
|
| ||
|
| Time. | |
|
|
| |
|
| Set the time when the tariff period ends, | |
End Time | 0000 to 2359 | using the 24 hour clock format (00:00 to | |
23:59). The End Time cannot equal the Start | |||
|
| ||
|
| Time. | |
|
|
|
© 2014 Schneider Electric All Rights Reserved | 87 |