<In case of SP80>

Check

Outdoor

Check and troubleshooting

code

LED display

(Item without special mention Indicates part of outdoor unit.)

 

 

 

[P19]

<Display 1> <Display 2>

[4-way valve reversal error]

¡¥

¡

¥

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature sensor check

 

¡

l

 

Does 4-way valve

 

 

 

 

 

YES

 

 

TE sensor CN601

 

l

l

 

work correctly?

 

 

 

 

 

 

 

TS sensor CN600

 

 

¡

¥

 

(Check pipe temp. etc.

 

 

 

Indoor TC sensor

 

 

in cooling/heating operation.)

 

 

 

 

 

 

 

 

 

 

Defect Correct and repair

 

¡

¡

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the coil resistance value

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

of 4-way valve between

 

 

 

Replace coil of 4-way valve.

 

 

 

 

 

 

 

1.3kand 1.6 k?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check operation of

Error

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board.

 

 

 

 

outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

Defect replace

 

 

 

 

(See below.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check 4-way valve.

 

 

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check method of outdoor P.C. board operation (Self-holding valve type)

1)Set SW804 of Dip switch as the following figure and then push SW801 for approx. 1 second to check exchange operation to cooling cycle/heating cycle.

Power is turned on for approx. 10 seconds.

In case of operating with the coil of 4-way valve connected to CN701, take interval over 1 minute before re-operation; otherwise it may cause overheat of the coil.

2)After check, turn off all the Dip switch SW804.

 

Exchange to cooling cycle

 

Exchange to heating cycle

SW804 SW801

CN701

SW804 SW801

CN701

 

4

 

1

 

4

 

1

 

3

 

 

 

3

 

 

ON

2

Push

 

ON

2

Push

 

1

4

1

4

 

 

 

DC200V or more

 

 

 

DC200V or more

Note) Check by tester

Analog tester : Good if over DC200V

Digital tester : Good if the maximum voltage is over DC200V though the varied voltage may be displayed.

In cooling operation, [P19] error may happen when the refrigerant pressure rose abnormally. In this case, remove the cause of pressure rising and then diagnose the error again.