12-4. Outdoor Unit

12-4-1. Refrigerant Recovery Control

The “ozone destruction coefficient” of HFC refrigerant is 0 and the discharge regulation is set as anathermal effect gas.

To this model, a switch which can perform the refrigerant recovery (pump down) by the outdoor unit is mounted so that it is easy to react against the environment at reinstalling or rejection time.

[Operation method]

<SP56>

1)See the mode of the indoor unit to fan mode.

2)Push the refrigerant recovery switch (SW802) of the outdoor unit for approx. 2 seconds. The cooling operation starts. (This operation finishes after 10 minutes.)

3)After operation for 3 minutes or more, close the valve at liquid side.

4)After recovering refrigerant, close the valve at gas side.

5)When keeping pushed the refrigerant recovery SW again for approx. 2 seconds, the outdoor unit stops.

6)Stop the indoor unit and then turn off the power supply.

Sub SW P.C. board of

model with 3HP or below

 

SW802

Refrigerant recovery

 

SW

ON

 

 

SW801

Exchange

Existing

to Cooling

piping

only

 

Power saving

Refrigerant recovery

SW

N

Sub SW P.C. board

NOTE

The electric portion of the refrigerant recovery SW on the sub-board is electrified, therefore be careful to an electric shock.

<SP80>

1)Set the mode of the indoor unit to fan mode.

2)Set all DIP switch SW804 to OFF (Initial status) and then push the button switch SW801 for approx. 1 second.

The cooling operation starts.

(During this time, D805 (Green LED) flashes.) This operation finishes by 10 minutes.

3)After operation for 3 minutes or more, close valve at liquid side.

4)After recovery of refrigerant, close valve at gas side.

5)Push the button switch SW801 again for approx. 1 second. The outdoor unit stops.

6)Stop the indoor unit and then turn off the power supply.

W804: All OFF (As initial status)

SW801: Push for 1 second.

 

4

ON

 

3

 

 

2

 

 

1

The D805 (Green LED) flashes.

D800

 

 

 

 

 

 

D801

 

 

 

 

 

 

D802

 

 

 

 

 

 

D803

 

 

 

 

 

 

D804

 

 

 

 

 

4

D805

 

 

 

ON

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

4

 

 

 

 

 

3

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 