nSetup of external static pressure

Be sure to set up a tap change based upon the resistance (external static pressure) of the duct to be connected.

To set up a tap change, follow to the basic operation procedure

(1 2 3 4 5 6 ).

Specify [5d] to the item code in procedure 3.

For the setup data of procedure 4, select a setup data of the external static pressure to be set up from the following table.

<Change on wired remote controller>

Setup data

External static pressure

 

 

 

0000

10 Pa

Standard (At shipment)

 

 

 

0001

20 Pa

High static pressure 1

 

 

 

0003

35 Pa

High static pressure 2

 

 

 

0006

50 Pa

High static pressure 3

 

 

 

When wireless remote controller is used

Change the external static pressure setting with the DIP switch on the receiver section P.C. board.

For details, refer to the manual of the wireless remote controller kit.

The settings can also be changed with the switch on the indoor microcomputer P.C. board.

However, once the setting is changed, setting to 0001 or 0006 is possible but setting to 0000 requires a setting data change to 0000 using the wired remote controller (separately sold) with the normal switch setting (factory setting).

SW501-1

SW501-2

MCU (IC501)

Setup data

SW501-1

SW501-2

 

 

 

0000

OFF

OFF

(Factory shipping)

 

 

 

 

 

0001

ON

OFF

 

 

 

0003

OFF

ON

 

 

 

0006

ON

ON

 

 

 

To restore the factory settings

To return the DIP switch settings to the factory settings, set SW501-1 and SW501-2 to OFF, con- nect a separately sold wired remote controller, and then set the data of CODE No. [5d] to “0000” in “Setup of external static pressure” on this page.