Toshiba RAV-SP404ATZG-E Coil heating control, No power-ON Continuous ON L Continuous ON H

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 66
Image 66

2)Heating fan control

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (From Min. W1 to Max. are controlled according to the following table.)

During 3 minutes after start-up, the fan is fixed with the maximum fan tap corresponding to zone in the following table.

After then the fan is controlled by temperature of TE sensor.

ƒIf status, TE > 24°C continues for 5 minutes, the operation stops.

This status is same to the usual Thermo-OFF which has no alarm display, and the fan restarts after 2 minutes and 30 seconds.

This intermittent operation is not abnormal.

When the above status occurs frequently, it is considered that the filter of suction part of the indoor unit is stain.

Clean the filter and then restart the operation.

TE [˚C]

–2 tap/20 seconds STOP timer count

24

–2 tap/20 seconds

21

–1 tap/20 seconds

18

rpm hold

15

+1 tap/20 seconds

 

Temp. range

f < 38.9Hz

38.9Hz f < 67.6Hz

67.6Hz f

 

 

 

 

 

 

 

10°C

TO

W7

W8

W9

 

 

 

 

 

 

 

5

TO < 10°C

WA

WB

WD

 

 

 

 

 

 

Maximum

–5

TO < 5°C

WE

WF

WF

 

 

 

 

 

 

 

 

TO < –5°C

WE

WF

WF

 

 

 

 

 

 

 

 

TO error

WE

WF

WF

 

 

 

 

 

 

5.Coil heating control

1)This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent slackness of the refrigerant inside of the compressor.

2)As usual, turn on power of the compressor for the specified time before a test run after installation, otherwise a trouble of the compressor may be caused.

As same as a test run, it is recommended to turn on power of the compressor beforehand when starting operation after power of the compressor has been interrupted for a long time.

3)Coil heating is controlled by TD and TE sensor.

4)The power is turned off when TD is 30°C or more.

TE [˚C]

0

–1

–6

–7

No power-ON

Continuous ON (L)

Continuous ON (H)

L

H

SP40, SP45

10W and equivalent

30W and equivalent

– 66 –

Page 66
Image 66
Toshiba RAV-SP404ATZG-E, RAV-SP804ATZG-E, RAV-SP804ATZ-E Coil heating control, No power-ON Continuous ON L Continuous ON H