Toshiba RAV-SP564ATZ-E Outdoor Unit, Super Digital Inverter, Model name, Outdoor unit, Rav-Sp

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 17
Image 17

1-2. Outdoor Unit

<Super Digital Inverter>

Model name

 

Outdoor unit

RAV-SP

404AT(Z)(ZG)-E

 

454AT(Z)(ZG)-E

564AT(Z)(ZG)-E

804AT(Z)(ZG)-E

 

 

 

 

 

 

 

 

 

Power supply

 

 

 

 

 

1 phase 230V (220 – 240V) 50Hz

 

 

 

 

(Power exclusive to outdoor is required.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

 

 

 

 

Hermetic compressor

 

 

 

 

 

 

 

 

 

Compressor

Motor

 

(kW)

1.1

 

1.1

1.1

2.0

 

 

 

 

 

 

 

 

 

 

Pole

 

 

4

 

4

4

4

 

 

 

 

 

 

 

 

 

Refrigerant charged

 

(kg)

1.0

 

1.0

1.4

2.1

 

 

 

 

 

 

 

 

Refrigerant control

 

 

 

 

Pulse motor valve

 

 

 

 

 

 

 

 

 

 

 

Standard length

(m)

7.5

 

7.5

7.5

7.5

 

 

 

 

 

 

 

 

 

 

Min. length

 

(m)

5

 

5

5

5

 

 

 

 

 

 

 

 

Inter

Max. total length

(m)

30

 

30

50

50

 

 

 

 

 

 

 

 

connecting

Additional refrigerant charge

 

20g/m

 

20g/m

20g/m

40g/m

pipe

 

 

under long piping connector

 

(21m to 30m)

 

(21m to 30m)

(21m to 50m)

(31m to 50m)

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

Outdoor lower

(m)

30

 

30

30

30

 

 

 

 

 

 

 

 

 

difference

Outdoor higher

(m)

30

 

30

30

30

 

 

 

 

 

 

 

 

 

 

 

 

 

Height

 

(mm)

550

 

550

550

890

Outer

 

 

 

 

 

 

 

 

Width

 

(mm)

780

 

780

780

900

dimension

 

 

 

 

 

 

 

 

 

 

 

Depth

 

(mm)

290

 

290

290

320

 

 

 

 

 

 

 

 

 

Appearance

 

 

 

 

 

Silky shade (Muncel 1Y 8.5/0.5)

 

 

 

 

 

 

 

 

 

Total weight

 

 

(kg)

40

 

40

44

63

 

 

 

 

 

 

 

 

Heat exchanger

 

 

 

 

Finned tube

 

 

 

 

 

 

 

 

 

 

 

Fan

 

 

 

 

Propeller fan

 

 

 

 

 

 

 

 

Fan unit

Standard air flow

(m³/min.)

40

 

40

40

50

 

 

 

 

 

 

 

 

 

 

Motor

 

(W)

43

 

43

43

63

 

 

 

 

 

 

 

 

 

Connecting

Gas side

 

(mm)

12.7

 

12.7

12.7

15.9

 

 

 

 

 

 

 

 

pipe

Liquid side

 

(mm)

6.4

 

6.4

6.4

9.5

 

 

 

 

 

 

 

 

 

 

 

 

Sound pressure level

Cooling/Heating

(dB•A)

45 / 47

 

45 / 47

47 / 48

48 / 49

 

 

 

 

 

 

 

 

Sound power level

Cooling/Heating

(dB•A)

62 / 64

 

62 / 64

63 / 64

64 / 65

 

 

 

 

 

 

 

 

Outside air temperature, Cooling

(°C)

 

 

43 to

– 15°C

 

 

 

 

 

 

 

Outside air temperature, Heating

(°C)

15 to

– 15°C

15 to

– 20°C

 

 

 

 

 

 

 

 

 

– 17 –