<In case of SP80>

Check

Outdoor

Check and troubleshooting

code

LED display

(Item without special mention Indicates part of outdoor unit.)

 

 

 

[H01]

<Display 1> <Display 2>

[Compressor break down]

l¥

l

l

Is AC mains voltage correct?

NO

 

 

 

 

 

 

Correct power supply line.

 

¡

l

 

 

 

 

 

 

 

AC198 to 264V

 

 

 

 

l

l

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

¡

 

Is wire connection correct?

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lead

 

 

Check wire connection

 

 

 

 

(Board side, Compressor side),

 

 

 

and correct it.

 

 

 

 

Reactor lead, Power supply lead

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

Does an abnormal overload happen?

 

 

Remove and improve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the cause of overload.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H02] <Display 1>

<Display 2>

[Compressor lock]

 

 

 

 

 

l

l

 

 

 

 

 

 

 

 

 

 

l

¥

 

 

Is AC mains voltage correct?

NO

 

 

 

 

 

 

 

Correct power supply line.

 

¡

l

 

 

 

 

 

 

 

AC198 to 264V

 

 

 

 

 

 

 

 

 

 

l

l

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¡

¡

 

 

Is wire connection correct?

NO

 

 

 

 

 

 

 

 

 

Check wire connection

 

 

 

 

 

Compressor lead

 

 

 

 

 

 

 

 

 

 

 

 

 

(Board side, Compressor side),

 

 

and correct it.

 

 

 

 

 

Reactor lead, Power supply lead

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

Is compressor under correct conditions?

 

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defect

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there refrigerant stagnation?

 

Compressor lock Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

Does PMV correctly operate?

 

Check TE, TS sensors and PMV.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defect

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[H03]

<Display 1> <Display 2> [Current detection circuit error]

l¥

l

¥

 

 

 

Check outdoor P.C. board.

 

¡

l

 

 

 

Defect Replace

 

l

l

 

 

 

 

 

 

 

 

 

 

¡l

¡¡

– 98 –

Page 98
Image 98