12-1-6. Monitor Function of Remote Controller Switch

nCalling of sensor temperature display

<Contents>

Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller.

<Procedure>

1

TEST

CL

Push
+ buttons simultaneously for 4 seconds to
call the service monitor mode.

The service monitor goes on, the master indoor unit No. is displayed at first and then the temperature of item code ￿￿ is displayed.

 

ò

 

2 Push temperature set

TEMP.

buttons and then change

 

the item code of data to be monitored.

The item code list is shown below.

TEMP.

 

 

ON / OFF

 

TIMER SET

FAN

MODE

 

TIME

SAVE

VENT

FILTER

SET CL

SWING/FIX

UNIT LOUVER

RESET TEST

2 4 1 3

<Operation procedure>

 

Item code

Data name

Unit

 

 

 

 

data

01

Room temperature

°C

 

(Remote controller)

 

02

Indoor suction temperature (TA)

°C

unit

03

Indoor heat exchanger (Coil)

°C

Indoor

 

temperature (TCJ)

 

04

Indoor heat exchanger (Coil)

°C

 

 

temperature (TC)

 

 

F3

Filter sign time

×1h

 

 

 

 

 

 

1

 

2

 

3

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Returned to usual display

 

 

 

 

 

 

 

 

 

 

 

Item code

 

Data name

 

 

 

 

 

Unit

 

 

 

 

data

60

Outdoor heat exchanger (Coil) temperature (TE)

°C

61

Outside temperature (TO)

 

 

 

 

 

°C

unit

 

 

 

 

 

62

Compressor discharge temperature (TD)

 

 

°C

Outdoor

63

Compressor suction temperature (TS)

 

 

°C

 

 

 

 

65

Heat sink temperature (THS)

 

 

 

 

 

°C

 

6A

Operation current (× 1/10)

 

 

 

 

 

A

 

F1

Compressor calculated operation time

 

 

×100h

 

 

 

 

 

 

 

 

 

 

 

 

 

ò

3

Push UNIT LOUVER button to select the indoor unit to be monitored.

 

Each data of the indoor unit and its outdoor units can be monitored.

 

ò

4

TEST

Pushing button returns the status to the usual display.

1 The indoor discharge temperature of item code [F8] is the estimated value from TC or TCJ sensor.

Use this value to check discharge temperature at test run.

(A discharge temperature sensor is not provided to this model.)

The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.

If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] are not displayed.