Toshiba RAV-SM564SDT-E n Change of lighting time of filter sign, 1 → 2 → 3 → 4 → 5 →

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 125
Image 125

nChange of lighting time of filter sign

According to the installation condition, the lighting time of the filter sign (Notification of filter clean- ing) can be changed.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [01].

For the [Set data] in Procedure 4, select the setup data of filter sign lighting time from the following table.

Setup data

Filter sign lighting time

 

 

0000

None

 

 

0001

150H

 

 

0002

2500H (At shipment from factory)

 

 

0003

5000H

 

 

0004

10000H

 

 

nTo secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised.

Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the CODE No. in Procedure 3, specify [06].

For the set data in Procedure 4, select the setup data of shift value of detection tempera- ture to be set up from the table below.

Setup data

Detection temp shift value

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C (At shipment from factory)

 

 

0003

+3°C

 

 

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

nHow to set up power saving mode

SAVE

1.Push button for at least four seconds when the air conditioner is not working.

flashes. Indicates CODE No. “C2.”

2.Select an indoor unit to be set by pushing UNIT LOUVER (left side of the button).

Each time you push the button, unit numbers change as follows:

Unit No.

 

Unit No.

 

Unit No.

1-1

 

1-2

 

1-3

Unit No.

1-4

The fan of the selected unit runs.

3.Adjust the power save setting by pushing TIME / buttons. Each push of the button changes the power level by 1% within the range from 100% to 50%.

* The factory setting is 75%.

This indication may not be true for types other than 4-series outdoor unit.

Setting of power level in power saving mode

4.Determine the setting by pushing SET button.

5.Push TEST button to complete the setting.