Toshiba RAV-SP804ATZ-E Outdoor Control Circuit, Outdoor Controls, PMV Pulse Motor Valve control

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 57
Image 57

9. OUTDOOR CONTROL CIRCUIT

9-1. Outdoor Controls

<In case of RAV-SP56 and SP80 models>

1.PMV (Pulse Motor Valve) control

1)PMV is controlled between (SP56: 20 to 500, SP80: 30 to 500) pulsed during operation.

2)In cooling operation, PMV is usually controlled with the temperature difference between TS sensor and TC sensor aiming (SP56: 2 to 5K, SP80: 1 to 4K) as the target value.

3)In heating operation, PMV is usually controlled with the temperature difference between TS sensor and TE sensor aiming (SP56: –2 to 4K, SP80: 2 to 4K) as the target value.

4)When the cycle excessively heated in both cooling and heating operation, PMV is controlled by TD sensor.

The target value is 101°C for both cooling and heating operations in SP56, and 91°C for cooling opera- tion and 96°C for heating operation respectively in SP80.

REQUIREMENT

A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the compressor life.

In a case of trouble on the compressor, be sure to check there is no error in the resistance value or the refrigerating cycle of each sensor after repair and then start the operation.

2.Discharge temperature release control

1)When the discharge temperature did not fall or the discharge temperature rapidly went up by PMV control, this control lowers the operation frequency.

It subdivides the frequency control up to 0.6Hz to stabilize the cycle.

2)When the discharge temperature detected an abnormal stop zone, the compressor stops and then restarts after 2 minutes 30 seconds.

The error counting is cleared when the operation continued for A minutes. If the error is detected by B times without clearing, the error is determined and restarting is not performed.

The cause is considered as excessively little amount of refrigerant, PMV error or clogging of the cycle.

3)For displayed contents of error, confirm on the check code list.

 

TD [˚C]

 

 

 

 

 

 

 

 

Abnormal stop

 

 

 

 

 

 

 

(117)

111

 

 

 

 

 

 

 

Frequency normal down

 

 

 

 

 

 

 

(107)

109

 

 

 

 

 

 

 

Frequency slow down

 

 

 

 

 

 

 

(105)

106

 

 

 

 

 

 

 

Frequency hold

 

 

 

 

 

 

 

(102)

103

 

 

 

 

 

 

 

Frequency slow up

 

 

 

 

 

 

 

(93)

96

 

(Up to command)

 

 

 

 

 

 

SP56

SP80

 

As command is

 

 

 

 

 

 

 

 

 

 

 

SP56 in the parentheses

 

A

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

8

4

 

 

 

 

 

 

 

 

– 57 –

Page 57
Image 57
Toshiba RAV-SP804ATZ-E Outdoor Control Circuit, Outdoor Controls, PMV Pulse Motor Valve control, Requirement, SP56