Toshiba RAV-SM564SDT-E Optional Connector Specifications of Indoor P.C. Board, Function, Pin No

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 55
Image 55

– 55 –

Function

Humidifier output ()

Intilation output

HA

Option output

Outside error input

AUTO up/down grille ()

FILTER Option error / Humidifier setting ()

CHK

Operation check

DISP Exhibition mode

EXCT

Demand

Connector No.

Pin No.

Specifications

Remarks

 

 

 

 

CN66

1

DC12V

Humidifier output is ON when heating operation is performed, when thermostat is on, when the fan is on.

 

 

The setting of Humidifier provided + Drain pump ON is performed by short-circuit of CN70 or from the

2

Output (Open collector)

 

remote controller. (DN [40] = 0001)

 

 

 

 

CN32

1

DC12V

Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop operation

 

 

The single operation setting by FAN button on the remote controller is performed on the remote

2

Output (Open collector)

 

controller (DN [31] = 0000 0001)

 

 

 

 

 

1

ON/OFF input

HA ON/OFF input (J01:YES/NO=Pulse (At shipment from factory) /Static input selection)

 

 

 

 

 

2

0V

 

 

 

 

 

CN61

3

Remote controller prohibited input

Permission/Prohibition of remote controller operation stop is performed by input.

 

 

 

4

Operation output (Open collector)

Operation ON (Answer back of HA)

 

 

 

 

 

 

5

DC12V

 

 

 

 

 

 

6

Warning output (Open collector)

Warning output ON

 

 

 

 

 

1

DC12V

 

 

 

 

 

 

2

Defrost output (Open collector)

ON when outdoor unit is defrosted

 

 

 

 

CN60

3

Thermostat ON output (Open collector)

ON when real thermostat is on. (Compressor ON)

 

 

 

4

Cooling output (Open collector)

ON when operation mode is cooling system (COOL, DRY, Cooling/Heating automatic cooling)

 

 

 

 

 

 

5

Heating output (Open collector)

ON when operation mode is heating system (HEAT, Cooling/Heating automatic heating)

 

 

 

 

 

6

Fan output (Open collector)

ON when indoor fan is on. (When air cleaner is used) OFF while clean operation is performed.

 

 

 

 

 

1

DC12V

 

 

 

 

 

CN80

2

NC

Generate the warning code “L30” (continuously for 1 minute) and stop the operation forcibly.

 

 

 

 

 

3

Outside error input

 

 

 

 

 

 

1

DC12V

 

 

 

 

 

 

2

Panel operation input

The grille is controlled according to up/down operation from the remote controller.

 

 

 

CN20

3

Panel up output (Open collector)

Setting of automatic up/down grille provided is performed on the remote controller.

 

4

Panel down output (Open collector)

(DN [30] = 0000 0001)

 

 

 

 

 

 

 

5

0V

 

 

 

 

 

 

1

 

Selection of option error input (Protective operation display of device attached to outside) or Humidifier

 

 

setting input (Vaporizing + Drain pump ON)

CN70

 

 

2

0V

Humidifier is set at shipment from factory.

 

 

Setting of option error input is performed on the remote controller. (DN [2A] = 0002 0001)

 

 

 

 

CN71

1

 

This check is used to check indoor operation. (Performs operation of indoor fan “H”, Louver horizontal

 

 

2

0V

and Drain pump ON without communication with outdoor and remote controller)

 

 

 

 

 

CN72

1

 

Communication is available by indoor unit and remote controller only.

 

 

2

0V

 

 

 

 

 

 

CN73

1

Demand input

Indoor unit forced thermostat OFF operation

 

 

2

0V

 

 

 

 

 

 

 

8-3. Optional Connector Specifications of Indoor P.C. Board

This option is not provided to oversea models.

Page 55
Image 55
Toshiba RAV-SM564SDT-E Optional Connector Specifications of Indoor P.C. Board, Function, Connector No, Pin No, Remarks