Toshiba RAV-SM564SDT-E, RAV-SP804ATZG-E, RAV-SP804ATZ-E Existing pipe NO * Use a new pipes NO

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 41
Image 41
(Airtight test), Vacuum dry, Refrigerant charge, Gas leak check
Trial run
ON
3 HP
Switch
Bit 3 of SW802
In case of twin, also be sure to flash the branching pipe.
Note]
For cooling the pipes and recovering of oil
Was not largely discolored oil or
a large quantity of remains discharged? (When the oil deteriorates, the color of the oil changes to muddy and black color.)
YES
￿ Connect the indoor/outdoor units to the existing pipe.
• Use a flare nut attached to the main unit for the indoor/outdoor units.
(Do not use the flare nut of the existing pipe.)
Re-machine the flare machining size to size for R410A.
￿ In case that the gas pipe Ø19 mm is used for the outdoor unit of SM803 (3 HP) or higher:
(Gas pipe size of our R410A model 3 is Ø15.9 mm)
Turn the existing pipe switch on the cycle control P.C board of the outdoor unit to ON side.
At shipment from factory OFF ON for existing pipe (Refer to the table below.) (Be sure to set the contents in the table below in order to restrict the refrigerating cycle pressure of the equipment in the pipe standard.)
Existing pipe SW
• Refrigerant recovery: Pump down method
Remove the existing air conditioner from the piping and carry out flashing (nitrogen pressure 0.5 Mpa) to remove the remains inside of the pipe.
7-6-5. Final Installation Checks
Is there no scratch or dent on the existing pipes?
Is it possible to operate the existing air conditioner?
YES
After the existing air conditioner operated in cooling mode for approx. 30 minutes or longer*, recover the refrigerant.

Existing pipe: NO * Use a new pipes.

NO

Nitrogen gas pressure 0.5 Mpa

(If there is discharge of remains,

it is judged that there is a large quantity of remains.)

NO

Clean the pipes or use the new pipes.

If you are in trouble of

pipe cleaning, please contact us.

Piping necessary to change the flare nut/ machining size due to pipe compression.

1) Flare nut width: H

(mm)

H

Copper pipe

Ø6.4

Ø9.5

Ø12.7

Ø15.9

Ø19.0

outer dia.

 

 

 

 

 

 

 

 

 

 

 

For R410A

17

22

26

29

36

 

 

 

 

 

 

For R22

Same as above

24

27

Same

 

 

 

 

 

as above

2) Flare machining size: A

(mm)

A

Copper pipe

Ø6.4

Ø9.5

Ø12.7

Ø15.9

Ø19.0

outer dia.

 

 

 

 

 

 

 

 

 

 

 

For R410A

9.1

13.2

16.6

19.7

24.0

For R22

9.0

13.0 16.2 19.4 23.3

Becomes large a little for R410A

Do not apply the refrigerator oil to the flare surface.

– 41 –

Page 41
Image 41
Toshiba RAV-SM564SDT-E, RAV-SP804ATZG-E, RAV-SP804ATZ-E, RAV-SP804AT-E, RAV-SP564ATZ-E Existing pipe NO * Use a new pipes NO