12-4-2. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.)

The following settings are available by DIP switch setup and jumper line setup.

<SP56>

Function

 

 

 

 

Setting position

Control contents

 

 

 

 

 

 

 

 

 

 

 

Existing piping

 

 

SW801

Turn off the switches. (Ø19.1 existing pipes cannot be used.)

setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save

 

 

 

 

 

 

 

 

 

When using the power saving function, turn on switches.

 

 

 

 

 

 

 

 

 

The control to lower the compressor frequency (approx. -10%) is performed

setup

 

1 2 3

 

 

 

 

 

by indoor heat exchanger temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing pipe setting

 

Cooling-only

 

 

 

 

 

 

 

 

When using the outdoor unit as a cooling-only machine, turn on switches.

 

 

 

 

 

 

 

 

Power saving setting

 

 

 

 

 

 

 

 

(“OF” of DN cord on the remote controller also can be used for changing the

setup

 

 

 

 

 

 

 

 

Cooling only setting

 

 

 

 

 

 

 

 

machine to the cooling-only model.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<SP80>

Function

 

 

 

 

 

Set position

 

Control contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when mounting a duct to the discharge port of the

 

 

 

 

 

 

 

outdoor unit. Add 3 taps to the upper limit value of the outdoor fan tap.

High static

 

 

 

 

 

 

The operation is performed with

 

 

 

 

 

 

 

 

 

 

(Max: Upper fan: 890 rpm / Lower fan: 910 rpm (WF)).

 

 

pressure setup

 

 

 

 

 

 

 

 

 

SW802

 

In this case, the upper limit value of static pressure for duct is 5Pa or less on

 

 

 

 

 

 

 

 

4

High static pressure setup

25°C degrees and please use straight duct.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In this case, the outdoor noise level may increase.

 

 

 

 

 

 

 

Existing piping setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

Turn the switch to ON when Ø19.1 is used for the existing pipe.

Existing

 

 

 

 

Power save setup

 

 

 

 

2

 

 

 

 

 

 

 

 

In this case, the heating capacity may lower according to outside temp. and

 

 

 

piping setup

 

ON

 

 

1

Snow-proof fan control

 

 

 

indoor temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power save

 

 

 

 

 

 

Turn the switch to ON when using the power save function.

 

 

 

 

 

 

The control to lower the compressor frequency (Approx. –10%) is performed

setup

 

 

 

 

 

 

 

 

all are OFF at shipment.

by indoor heat exchanger temp. in heating operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When snow enters from clearance of the fan guard or heat exchanger into

Snow-proof

 

 

 

 

 

 

blast path and it is accumulated, the control to prevent generation of motor

 

 

 

 

 

 

lock is validated.

 

 

 

 

fan control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When outside temp. is below 0°C though the compressor stops, the outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan operates with W5.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Defrost

 

 

 

 

 

J805, J806

The defrost interval is cut to shorten it than the standard status.

 

 

 

 

 

For contents of control and cutting method, refer to Section

time change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9-1-10. Defrost control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When it is needed to lower the maximum value of the compressor frequency,

 

 

 

 

 

 

 

cut the jumper line. Max. frequency at cooling/heating is lowered.

 

 

 

 

 

 

 

In this case the Max. capacity decreases.

 

 

 

 

 

 

 

 

 

Max. frequency of compressor

 

 

 

 

Max. frequency

 

 

 

 

 

J807

 

 

 

 

 

 

 

change

 

 

 

 

 

 

 

 

RAV-SP80

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard status

 

72.0

 

99.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When J807 is cut

 

72.0

 

79.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling-only

 

 

 

 

 

 

When using the air conditioner as a cooling-only conditioner, cut the jumper

 

 

 

 

 

J808

line. (An air conditioner can be changed to cooling-only conditioner by “0F” of

setup

 

 

 

 

 

 

 

 

 

 

 

DN code on the remote controller.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 