13-4. Address Setup (Manual setting from remote controller)

In case that addresses of the indoor units will be determined prior to piping work after cabling work

Set an indoor unit per a remote controller.

Turn on power supply.

(Example of 2-lines cabling)

(Real line: Cabling, Broken line: Refrigerant pipe)

Outdoor

Outdoor

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

1

2

3

Indoor

Indoor

Indoor

Indoor

A B

 

A B

 

A B

 

A B

 

Line address 1

 

 

 

1

 

2

 

 

2

 

 

Indoor unit address 1

 

 

 

2

 

1

 

 

2

 

 

Group address 1

 

 

 

2

 

2

 

 

2

 

 

1

Push

SET

+

CL

+

TEST

buttons simultaneously

A B

 

 

 

 

 

 

 

 

 

for 4 seconds or more.

 

 

Remote controller

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

(

Line address)

 

 

 

For the above example, perform setting by

 

/

buttons,

connecting singly the wired remote controller

 

Using the temperature setup

 

without remote controller inter-unit cable.

 

set 12 to the item code.

 

 

Group address

 

3

 

 

 

 

 

 

 

 

 

 

Individual

: 0000

 

Using timer time

/ buttons, set the line address.

Master unit : 0001

In case of group control

Sub unit

: 0002

4

Push SET

button. (OK when display goes on.)

 

 

 

5

(

Indoor unit address)

/

buttons, set 13

to the item code.

 

 

Using the temperature setup

 

6

Using timer time

/ buttons, set 1 to the line address.

 

 

7

Push SET

button. (OK when display goes on.)

 

 

 

8

(

Group address)

/

buttons, set 14

to the item code.

 

 

Using the temperature setup

 

9

Using timer time

/ buttons, set 0000 to Individual, 0001 to Master unit, and 0002 to sub unit.

10

 

Push SET

button. (OK when display goes on.)

 

 

 

11

 

Push TEST button.

 

 

 

 

 

Setup completes. (The status returns to the usual stop status.)

TEMP.

ON / OFF

2, 5, 8

END 11

1

<Operation procedure>

FILTER RESET TEST

TIMER SET

FAN

MODE

TIME

SAVE

VENT

SET CL

SWING/FIX

UNIT LOUVER

3, 6, 9 4, 7, 10

1 2 3 4 5 6 7 8 9 10 11 END

– 139 –