[C06 error] (TCC-LINK central controller)

NO

Are U3 and U4 communication lines normal?

YES

Correct communication line.

1

NO

Is connection of connector normal?

Correct connection of connector.

YES

1

TCC-LINK central:

CN51 of TCC-LINK adapter P.C. board (MCC-1440) and CN050 of indoor P.C. board

Are A and B communication lines normal?

YES

Is there no connection error of power supply cable?

NO

Is not the source power supply turned on?

YES

NO

 

 

 

 

 

 

Check connection of A and B terminal blocks.

 

 

 

 

 

 

 

 

Correct communication line of remote controller.

 

 

 

 

 

 

 

 

 

 

 

YES

Correct power wiring.

NO

Turn on the source power supply.

Did a power failure occur?

NO

Is the network address changed

from the remote controller?

NO

Is there no noise source?

NO

Can the other indoor units

be normally controlled from the central controller? Or is the operation status of indoor unit reflected?

YES

YES

YES

YES

Uncontrolled

(Same to others)

Clear the check code.

Eliminate noise, etc.

Check central controller.

Defect Replace

Can the indoor unit be normally controlled

from the remote controller?

YES

Check power supply transformer on

TCC-LINK adapter P.C. board (MCC-1440).

Defect Replace

Uncontrolled

 

 

 

 

 

 

Check indoor P.C. board (MCC-1570).

 

 

 

 

 

 

 

 

Defect Replace

 

 

 

 

 

 

 

 

 

 

 

– 89 –

Page 89
Image 89