Toshiba RAV-SP404ATZ-E, RAV-SP804ATZG-E, RAV-SP804ATZ-E Outline of specifications, Remarks

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 53
Image 53

No.

Item

Outline of specifications

Remarks

 

 

 

 

 

 

15

Central control mode 1)

Setting at the centerl controller side enables to select the

 

 

 

 

selection

contents which can be operated on the remote controller

 

 

 

 

 

at indoor unit side.

 

 

 

 

2)

Setup contents

 

 

 

 

 

• 64 line central controller (TCB-SC642TLE2)

Display at remote

 

 

 

 

 

[Individual]: Operated on the remote controller

controller side

 

 

(Priority to second pushing)

(No display)

 

 

[Central 1]: ON/OFF operation cannot be operated on

[Central

 

] goes on

 

 

the remote controller.

 

 

 

 

 

[Central 2]: ON/OFF, mode selection, temp. setup

[Central

 

] goes on

 

 

operations cannot be operated on the

 

 

 

 

 

remote controller.

 

 

 

 

 

[Central 3]: Mode selection and temp. setup operations

[Central

 

] goes on

 

 

cannot be operated on the remote controller.

 

 

 

 

 

[Central 4]: Mode selection cannot be operated on the

[Central

 

] goes on

 

 

remote controller.

 

 

 

In case of the wireless type, the display lamp does not change but the contents are same. If operating an item which is prohibited by the central control mode from the remote controller, it is notified with the receive sound, Pi, Pi, Pi, Pi, Pi (5 times).

16

Energy-saving

1)

Selecting [AUTO] mode enables an energy-saving to be

 

control

 

operated.

 

 

 

 

 

 

 

(In case of connect-

2)

The setup temperature is shifted (corrected) in the range

 

ing SDI outdoor unit)

 

 

not to lose the comfort ability according to input values of

 

 

 

 

 

 

various sensors.

 

 

 

 

 

 

 

 

3) Data (Input value room temp. Ta, Outside temp. To, Air

 

 

 

 

 

volume, Indoor heat exchanger sensor temp. Tc) for

 

 

 

 

 

20 minutes are taken the average to calculate correction

 

 

 

value of the setup temperature.

 

 

 

 

 

 

 

 

4)

The setup temperature is shifted every 20 minutes, and

 

 

 

 

 

the shifted range is as follows.

 

 

 

 

 

 

 

 

 

In cooling time: +1.5 to – 1.0K

 

 

 

 

 

 

 

 

 

In heating time: –1.5 to +1.0K

 

 

 

 

 

 

 

 

 

 

17

Max. frequency cut

1)

This control is operated by selecting [AUTO] operation mode.

 

control

2)

COOL operation mode:

3) HEAT operation mode:

 

 

 

 

 

It is controlled according to the

It is controlled according to the

 

 

 

following figure if To < 28°C.

following figure if To > 15°C.

 

 

 

 

 

 

 

 

 

 

 

Max. frequency is

 

 

Ta(˚C)

 

 

 

Ta(˚C)

 

 

 

restricted to approximately

 

 

Normal control

 

 

 

 

 

the rated heating frequency

 

 

 

+4

 

Tsh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+3

 

 

 

–3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tsc

 

 

 

–4

 

 

 

 

 

 

 

 

 

 

 

Normal control

 

 

 

Max. frequency is

 

 

 

 

 

 

 

 

 

restricted to approximately

 

 

 

 

 

 

 

 

 

 

the rated cooling frequency

 

 

 

 

 

 