3. Outdoor fan control

Revolution frequency allocation of fan taps [rpm]

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP56

200

250

300

400

480

500

520

560

640

670

700

750

800

880

980

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP80

200

230

260

300

340

380

420

460

520

570

600

630

670

710

740

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-1) Cooling fan control

<SP56>

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. It is controlled by every 1 tap of DC fan control (15 taps).

Only for 60 seconds after start-up of operation, it is fixed by the maximum fan tap corresponded to the zone in the following table, and then the fan is controlled by temperature of TE sensor.

ƒWhen temperature of TD sensor became high sufficiently, it is controlled so that the fan revolution frequency will become higher ignoring TE sensor temperature.

TE [˚C]

+1 tap / 20 sec

Up to the maximum

revolution frequency of each zone

Operation with W1 in case of fan-OFF

32

Revolution frequency hold

29

–1 tap / 20 sec

Down to the minimum

revolution frequency of each zone

TD [˚C]

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

85

 

 

 

with WF

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

 

 

Operation with

 

 

 

 

 

 

 

 

 

 

 

 

the maximum tap

 

 

75

 

 

 

of each zone

 

 

65

 

 

 

Normal fan control

 

 

 

 

 

 

 

 

 

 

 

 

by TE sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20 Hz

20Hz

 

45Hz

Temp. range

or lower

to 45Hz

 

or higher

 

 

 

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

 

38°C TO

W6

WB

W7

WE

 

W9

WF

 

 

 

 

 

 

 

 

 

28°C

TO < 38°C

W5

WA

W6

WD

 

W8

WE

 

 

 

 

 

 

 

 

 

15°C

TO < 28°C

W3

W7

W4

W9

 

W6

WB

 

 

 

 

 

 

 

 

 

5.5°C

TO < 15°C

W2

W5

W3

W7

 

W5

W9

 

 

 

 

 

 

 

 

0°C TO < 5.5°C

W1

W3

W2

W5

 

W3

W7

 

 

 

 

 

 

 

 

–5°C TO < 0°C

W1

W2

W1

W3

 

W2

W4

 

 

 

 

 

 

 

 

TO < –5°C

OFF

OFF

OFF

OFF

 

W1

W3

 

 

 

 

 

 

 

 

TO error

W1

WB

W1

WE

 

W1

WF

 

 

 

 

 

 

 

 

 

 

<SP80>

The outdoor fan is controlled by TL sensor, TO sensor and the operation frequency.

The outdoor fan is controlled by every 1 tap of DC fan control (15 taps).

Only for 60 seconds after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TL sensor.

TL [˚C]

 

WF tap

58

 

55

 

 

+1 tap / 20 sec

 

Up to the maximum

 

revolution frequency of each zone

38

Revolution frequency hold

35

–1 tap / 20 sec

 

 

Down to the minimum

 

revolution frequency of each zone

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

 

 

 

Min.

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

38°C TO

W6

WC

W8

WE

WA

WE

 

 

 

 

 

 

 

29°C TO < 38°C

W5

WB

W7

WD

W9

WD

 

 

 

 

 

 

 

15°C TO < 29°C

W4

W8

W6

WA

W8

WC

 

 

 

 

 

 

 

5°C TO < 15°C

W3

W6

W5

W8

W7

WA

 

 

 

 

 

 

 

0°C TO < 5°C

W2

W4

W4

W6

W5

W8

 

 

 

 

 

 

 

–4°C TO < 0°C

W2

W3

W3

W5

W4

W6

 

 

 

 

 

 

 

TO < –4°C

OFF

OFF

OFF

W2

OFF

W3

 

 

 

 

 

 

 

TO error

OFF

WC

OFF

WE

OFF

WE

 

 

 

 

 

 

 

– 58 –

Page 58
Image 58
Toshiba RAV-SP804AT-E Outdoor fan control, Cooling fan control SP56, Revolution frequency allocation of fan taps rpm