Error mode detected by outdoor unit

The check code has been ramified from “4 series” and after.

The ramified check code is displayed only when both the indoor unit and the outdoor unit are “4 series” and after. (Ex. Combination of RAV-SM804UT-E with RAV-SP804AT-E)

When the indoor unit is 3 series and before, the conventional check code is displayed.

(Ex. Combination of RAV-SM802BT-E and RAV-SP804AT-E: Outdoor unit only is “4 series”.)

 

 

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

Check code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judgment and measures

Indoor unit

 

Cause of operation

Status of

Condition

 

 

 

 

 

 

 

 

air conditioner

 

 

before

 

after

 

 

 

 

 

 

 

 

 

 

 

 

3 series

 

4 series

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F04

 

F04

Disconnection, short-circuit of

Stop

Displayed when

1.

Check discharge temp. sensor (TD).

 

discharge temp. sensor (TD)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

F06

 

F06

Disconnection, or short-circuit of

Stop

Displayed when

1.

Check temp. sensor (TE).

 

outdoor temp. sensor (TE)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F07

Disconnection, or short-circuit of

Stop

Displayed when

1.

Check temp. sensor (TL).

 

 

outdoor temp. sensor (TL)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F12

Disconnection, or short-circuit of

Stop

Displayed when

1.

Check suction temp. sensor (TS).

 

 

suction temp. sensor (TS)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F15

Miss-mounting of outdoor temp.

Stop

Displayed when

1.

Check temp. sensor (TE, TS).

 

 

sensor (TE, TS)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

F08

 

F08

Disconnection, or short-circuit of

Continue

Displayed when

1.

Check outside temp. sensor (TO).

 

outside temp. sensor (TO)

error is detected

2.

Check outdoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

L29

 

F13

Disconnection, or short-circuit of heat

Stop

Displayed when

1.

Check outdoor P.C. board.

 

sink temp. sensor (TH)

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F31

Outdoor P.C. EEPROM error

Stop

Displayed when

1.

Check outdoor P.C. board.

 

 

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L10

Incorrect setting of service P.C. board

Stop

Displayed when

1.

Outdoor service P.C. board

 

 

error is detected

 

Check model type setting jumper wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L29

Communication error between MCUs

Stop

Displayed when

1.

Check outdoor P.C. board.

 

 

on outdoor P.C. board

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat sink overheat error

 

Displayed when

1.

Check screw tightening between PC. Board and heat

 

 

P07

Heat sink temp. sensor detected

Stop

 

sink and check radiator grease.

 

 

error is detected

 

 

 

 

 

over the specified temperature.

 

2.

Check heat sink cooling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check gas leak.

 

 

 

Detection of gas leak

 

 

2.

Check whether the service valve is fully opened.

 

 

P15

Discharge temp. sensor (TD),

Stop

Displayed when

3.

Check PMV (Pulse Motor Valve).

 

 

 

Suction temp. sensor (TS) detected

error is detected

4.

Check broken pipe.

 

 

 

 

 

 

 

 

 

temperature over the specified temp.

 

 

 

 

 

 

 

 

5.

Check discharge temp. sensor (TD), suction temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

sensor (TS).

 

 

 

 

 

 

 

 

 

 

 

4-way valve inverse error

 

 

1.

Check operation of 4-way valve.

 

 

 

After heating operation has started,

 

 

2.

Check outdoor heat exchanger (TE), suction temp.

 

 

 

 

indoor heat exchanger temp. lowers

 

Displayed when

 

sensor (TS).

 

 

P19

 

under the specified temp.

Stop

 

 

 

 

 

error is detected

3.

Check indoor heat exchanger sensor (TC).

 

 

 

 

 

 

 

 

After heating operation has started,

 

 

4.

Check 4-way valve coil.

 

 

 

 

outdoor heat exchanger / suction

 

 

 

 

 

 

 

 

5.

Check PMV (Pulse Motor Valve).

 

 

 

 

temp. rises over the specified temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor break down

 

 

1.

Check power supply voltage. (AC198 to 264V)

H01

 

H01

Although operation has started,

Stop

Displayed when

2.

Overload operation of refrigerating cycle

 

 

operation frequency decreases and

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

operation stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lock

 

Displayed when

1.

Trouble of compressor (Lock, etc.): Replace compressor.

H02

 

H02

* Over-current detection after

Stop

2.

Wiring error of compressor (Open circuit)

 

error is detected

 

 

 

 

compressor start-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H03

 

H03

Current detection circuit error

Stop

Displayed when

1.

Check outdoor P.C. board. (AC current detection circuit)

 

error is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 80 –