4. Outdoor fan control

Allocations of fan tap revolutions [rpm]

 

W1

W2

W3

W4

W5

W6

W7

W8

W9

WA

WB

WC

WD

WE

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP40, SP45

200

300

350

410

480

500

560

640

670

700

750

800

800

840

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Cooling fan control

The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the operation. The outdoor is controlled by every 1 tap of DC fan control (15 taps).

Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap which corresponds to the zone in the following table.

After then the fan is controlled by TE sensor temperature.

ƒConsidering a case that TE sensor has come out of the holder, the fan is controlled so that revolution frequency of the fan increases regardless of TE if temperature of TD sensor has risen.

Operation with WE

TE [˚C]

TD [˚C]

32

29

 

 

“WF”

+1 tap/20 seconds

85

 

 

 

 

80

 

rpm hold

Operation with

 

 

75

maximum tap in

 

each zone

–1 tap/20 seconds

65

Usual fan control

 

 

Temp. range

f < 34.1Hz

34.1Hz

f < 58.6Hz

58.6Hz f

 

 

 

 

 

 

 

Min.

 

Max.

Min.

Max.

Min.

Max.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38°C

TO

 

W6

 

WB

W8

WD

WA

WF

 

 

 

 

 

 

 

 

 

 

32

TO < 38°C

W5

 

WA

W7

WC

W9

WF

 

 

 

 

 

 

 

 

 

 

15

TO < 32°C

W3

 

W7

W5

W9

W7

WB

 

 

 

 

 

 

 

 

 

 

5

TO < 15°C

W2

 

W5

W4

W7

W6

W9

 

 

 

 

 

 

 

 

 

 

 

1

TO <

5°C

W1

 

W3

W3

W5

W4

W7

 

 

 

 

 

 

 

 

 

 

–5

TO <

1°C

W1

 

W2

W2

W4

W3

W5

 

 

 

 

 

 

 

 

 

 

 

 

TO < –5°C

 

OFF

OFF

W3

W1

W4

 

 

 

 

 

 

 

 

 

 

 

TO error

 

W1

 

WF

W1

WF

W1

WF

 

 

 

 

 

 

 

 

 

 

 