Toshiba RAV-SP404ATZG-E, RAV-SP804ATZG-E service manual How to set contents of save operation, Push

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 122
Image 122

2.How to confirm the central control address (New function for AMT32E remote controller)

<Procedure> It can be confirmed even during operation or stopping.

1 Push UNIT LOUVER button for 4 seconds or more.

ò

2 In the frame at left side of the remote controller screen, the lighting set contents are displayed.

During unset time, ￿￿'' (At shipment from factory) is displayed.

ò

3 After lighting display for 3 seconds, the display automatically disappears.

If any button is pushed during display, immediately the display disappears and then the pushed button is displayed.

3. How to set contents of save operation

1

2

In combination with outdoor units before 4 series, the displayed setup value exchanges, but the real operation is “75% fixed”.

Push

SAVE

for 4 seconds or more during stop of the operation.

flashes.

UNIT LOUVER

Push (At the left side of the button) and select the unit to be set.

Every pushing the button, the unit No. changes.

The fan of the selected unit rotates and the louver swings.

 

UNIT No.

 

UNIT No.

UNIT No.

 

1–1

 

 

1–2

 

1–3

 

 

 

 

 

UNIT No. 1–4

 

 

 

 

 

 

 

3 Determine the capacity restricted value when pushing the save button of TIMER SET / .

Every pushing the button, the capacity restricted value can be set at 1% interval in the range between 100% and 50%.

The setting at shipment is 75%.

Setup value at saving

4 Push SET and then push TEST to finish the setup.

– 122 –

Page 122
Image 122
Toshiba RAV-SP404ATZG-E service manual How to set contents of save operation, Push UNIT LOUVER button for 4 seconds or more