Toshiba RAV-SP564ATZ-E, RAV-SP804ATZG-E Coil heating control, Heating fan control

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 59
Image 59

3-2) Heating fan control

The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (Control from minimum W1 to maximum (according to the following table))

For 3 minutes after the operation has started, the maximum fan tap corresponding to the zone in the following table is fixed and then the fan is controlled by temperature of TE sensor.

 

 

ƒ When TE 24°C continues for 5 minutes, the

TE [˚C]

compressor stops.

 

 

–2 taps / 20 sec. (Down to W1)

It is the same status as the normal THERMO

 

 

OFF without error display.

24

Stop timer count

The compressor restarts after approx. 2 minutes

 

 

–2 taps / 20 sec. (Down to W1)

30 seconds and this intermittent operation is not

21

 

abnormal.

 

 

–1 tap / 20 sec. (Down to W1)

In case that the status in item ƒ generates

18

 

frequently, stain on filter of the suction part of

 

 

Revolution frequency hold

the indoor unit is considered.

15

 

Clean the filter and then restart the operation.

+1 tap / 20 sec

 

 

 

(Up to the maximum tap of each zone)

 

 

 

 

<SP56>

<SP80>

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5.5°C TO < 10°C

WA

WC

WE

 

 

 

 

–5°C TO < 5.5°C

WD

WE

WF

 

 

 

 

TO < –5°C

WE

WF

WF

 

 

 

 

TO error

WE

WF

WF

 

 

 

 

 

20 Hz

20Hz

45Hz

Temp. range

or lower

to 45Hz

or higher

 

 

 

 

Max.

Max.

Max.

 

 

 

 

10°C TO

W7

W8

W9

 

 

 

 

5°C TO < 10°C

W9

WB

WD

 

 

 

 

–3°C TO < 5°C

WD

WD

WE

 

 

 

 

–10°C TO < –3°C

WE

WE

WE

 

 

 

 

TO < –10°C

WF

WF

WF

 

 

 

 

TO error

WF

WF

WF

 

 

 

 

4.Coil heating control

1)This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent stagnation of the refrigerant inside of the compressor.

2)As usual, turn on power of the compressor for the specified time before a test run after installation; otherwise a trouble of the compressor may be caused.

As same as a test run, it is recommended to turn on power of the compressor beforehand when starting operation after power of the compressor has been interrupted and left as it is for a long time.

3)SP80 judgment for electricity is performed by TD and TO sensors.

If TO sensor is defective, a backup control is automatically performed by TE sensor. For a case of defective TO sensor, judge it with outdoor LED display.

Using TD sensor and TE sensor, SP56 judges the power-on.

4)For every model, the power is turned off when TD is 30°C or more.

– 59 –

Page 59
Image 59
Toshiba RAV-SP564ATZ-E, RAV-SP804ATZG-E, RAV-SP804ATZ-E, RAV-SP804AT-E Coil heating control, Heating fan control