3-2. Outdoor Unit

 

 

RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E

 

RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E

 

 

Packed valve

Packed valve

 

Outer dia. ØA

Outer dia. ØB

TS sensor

 

PMV

 

(Pulse Motor Valve)

 

 

2-step muffler

TO sensor

(CAM-B30YGTF-2)

 

Ø19.05 × 200L

 

 

TD sensor

 

 

 

 

Strainer

4-way valve

TE

 

(STF-0108Z)

sensor

 

Muffler

Heat exchanger

 

Ø19 × L160

Ø8 ripple, 2 rows,

 

 

14 steps

Distributor

 

FP1.3 flat fin

Rotary compressor

 

 

 

(DA150A1F-20F)

 

 

 

 

R410A 1.0 kg

 

 

Cooling

 

 

Heating

RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E

 

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

(MPa)

(kg/cm²g)

Discharge

Suction

Indoor heat

Outdoor heat

drive revolution

Indoor

temp. conditions

 

 

(DB/WB) (°C)

 

 

exchanger

exchanger

frequency

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.68

0.94

27.3

9.6

61

12

11

43

47

HIGH

27 / 19

35 / –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.23

1.16

32.9

11.8

77

14

15

50

50

HIGH

32 / 24

43 / –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.34

0.70

13.7

7.1

36

4

2

8

44

LOW

18 / 15.5

–5 /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.38

0.70

24.3

7.1

65

7

39

4

49

HIGH

20 / –

7 / 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.39

1.03

34.6

10.5

83

20

54

16

49

LOW

30 / –

24 / 18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.95

0.26

19.9

2.7

90

–17

32

–19

90

HIGH

15 / –

–15 /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp meter becomes 2 times of No. of compressor revolutions (rps).

RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E

 

 

 

Pressure

 

 

Pipe surface temperature (°C)

Compressor

 

Indoor/Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

(MPa)

(kg/cm²g)

Discharge

Suction

Indoor heat

Outdoor heat

drive revolution

Indoor

temp. conditions

 

 

(DB/WB) (°C)

 

 

exchanger

exchanger

frequency

fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(rps)

 

 

 

 

 

Pd

Ps

Pd

Ps

(TD)

(TS)

(TC)

(TE)

 

Indoor

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.81

0.89

28.7

9.1

68

11

10

41

53

HIGH

27 / 19

35 / –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Overload

3.24

1.16

33.0

11.8

78

14

15

51

53

HIGH

32 / 24

43 / –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

1.34

0.70

13.7

7.1

36

4

2

8

44

LOW

18 / 15.5

–5 /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard

2.53

0.68

25.8

6.9

70

7

41

4

56

HIGH

20 / –

7 / 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

Overload

3.39

1.03

34.6

10.5

83

20

54

16

49

LOW

30 / –

24 / 18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low load

2.00

0.25

20.4

2.6

92

–17

33

–19

98

HIGH

15 / –

–15 /

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This compressor has 4-pole motor. The value when compressor frequency (Hz) is measured by a clamp meter becomes two times of No. of compressor revolutions (rps).

– 25 –

Page 25