Toshiba RAV-SP404ATZG-E, RAV-SP804ATZG-E Outline of specifications, Remarks, HA control

Models: RAV-SM564SDT-E RAV-SM454SDT-E RAV-SP404ATZ-E RAV-SP404ATZG-E RAV-SP404AT-E RAV-SP454ATZ-E RAV-SP454ATZG-E RAV-SP564AT-E RAV-SP454AT-E RAV-SP564ATZG-E RAV-SP564ATZ-E RAV-SP804AT-E RAV-SP804ATZ-E RAV-SP804ATZG-E

1 177
Download 177 pages 27.24 Kb
Page 52
Image 52

No.

Item

 

Outline of specifications

Remarks

 

 

 

 

 

12

HA control

1)

This control is connected to TV control or remote start/

In the group

 

 

 

stop I/F, etc, and start/stop are available by HA signal

operation, use this

 

 

 

input from the remote position.

control by

 

 

2)

This control outputs start/stop status to HA output

connecting to either

 

 

master or follower

 

 

 

terminal.

 

 

 

indoor unit.

 

 

3)

I/O specifications conform to JEMA regulations.

 

 

 

 

 

4)

This control outputs [Operation OFF (STOP) signal] to HA

 

 

 

 

output terminal while self-cleaning works. However selection

 

 

 

 

of [Operation ON (Operating) signal] is possible by changing

 

 

 

 

[0000 (At shipment)] of Item code (DN) [CC] to [0001].

 

 

 

 

In this case, if HA is input during self-clean operation during

 

 

 

 

operation of the air conditioner, the self-clean operation is not

 

 

 

 

performed. (Unit stops.)

 

 

 

 

 

13

Frequency fixed

<In case of wired remote controller>

Command frequency

 

operation (Test run)

1)

When pushing [CHK] button for 4 seconds or more,

is approximately [S7]

 

 

 

 

 

 

[TEST] is displayed on the display screen and the mode

 

 

 

 

enters in Test run mode.

 

 

 

2)

Push [ON/OFF] button.

 

 

 

3)

Using [MODE] button, set the mode to [COOL] or [HEAT].

 

 

 

 

• Do not use other mode than [COOL]/[HEAT] mode.

 

 

 

 

• During test run operation, the temperature cannot be

 

 

 

 

adjusted.

 

 

 

 

• An error is detected as usual.

 

 

 

 

• A frequency fixed operation is performed.

 

 

 

4)

After the test run, push [ON/OFF] button to stop the

 

 

 

 

operation. (Display in the display part is same as the

 

 

 

 

procedure in Item 1.)

 

 

 

5)

Push [CHK] button to clear the test run mode.

 

 

 

 

([TEST] display in the display part disappears and the

 

 

 

 

status returns to the normal stop status.)

 

 

 

 

 

 

14

Filter sign display

1)

The operation time of the indoor fan is calculated, the filter

[FILTER ] goes on.

 

(Except wireless type)

 

reset signal is sent to the remote controller when the

 

 

It is provided on the

 

specified time (2500H) has passed, and it is displayed on

 

 

separately sold type

 

LCD.

 

 

 

 

 

 

TCB-AX21E2.

2)

When the filter reset signal has been received from the

 

 

 

 

remote controller, time of the calculation timer is cleared.

 

 

 

 

In this case, the measurement time is reset if the

 

 

 

 

specified time has passed, and display on LCD

 

 

 

 

disappears.

 

 

 

 

 

 

– 52 –

Page 52
Image 52
Toshiba RAV-SP404ATZG-E, RAV-SP804ATZ-E Outline of specifications, Remarks, HA control, In case of wired remote controller