Xantrex Technology PV100S-208 manual Periodic Maintenance, Monthly Intervals or As Required

Models: PV100S-208

1 124
Download 124 pages 2.86 Kb
Page 102
Image 102
Periodic Maintenance

Preventative Maintenance

Periodic Maintenance

Xantrex Technology recommends that the following preventative maintenance procedures be carried out on the PV100S.

Monthly Intervals or As Required

Perform the following preventative maintenance tasks on a monthly basis or as required.

Aluminum Extrusion Heatsink

Inspect the aluminum extrusion heatsink and external cooling fan for accumulation of dirt and debris. Accumulation of dirt and debris on the aluminum extrusion heatsink and external cooling fan will decrease their ability to transfer heat, which may cause the PV100S to enter a fault state based upon an over-temperature alarm. Remove and clean if debris is present.

Fan Operation

Verify proper operation of the external cooling fan, located above the matrix aluminum extrusion heatsink. This fan operates when the K1 contactor is closed. If present, remove any debris from the fan.

Internal Circulation Fan

Verify the internal circulation fan (B2) is operating whenever there is utility power applied to the PV100S.

Inductor Enclosure Cooling Fan

Verify the inductor enclosure cooling fan operates whenever the PV100S is processing power. The airflow direction should be from the outside, forcing air into the enclosure. If present, remove any debris from the fan.

5–6

152379 Rev C

Page 102
Image 102
Xantrex Technology PV100S-208 manual Periodic Maintenance, Monthly Intervals or As Required, Aluminum Extrusion Heatsink